{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AP60-0UA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AP60-0UA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AP60-0UA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AP60-0UA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1036-1AP60-0UA0 power contactor, size S2, screw-type terminals, 22 kW at 400 V AC-2, 30 kW at 500 V, IP20 front.","salesMarkdown":"Rated for 22 kW at 400 V under AC-2 duty, it handles slip-ring motor starting and reversing. At 500 V it delivers 30 kW, and at 690 V it's rated for 11.4 kW — covering common 400 V and 690 V line supplies across 50/60 Hz networks. The main current circuit uses screw-type terminals, accepting solid conductors up to 4 mm² per clamp and stranded up to 25 mm². Auxiliary contacts are rated 10 A at 24 V, stepping down to 0.3 A at 220 V — enough for PLC-level signal switching. The AC-2 rating at 22 kW is the key selection number — it governs the contactor's ability to handle the higher inrush and arcing of slip-ring motors. AC-3 (not listed here) would be for standard squirrel-cage motors; if your load is a standard induction motor, verify the AC-3 rating separately. Maximum switching frequencies give a sense of duty cycle: 400 operations per hour for AC-2, 800 for AC-3, and 300 for the punishing AC-4 plugging/reversing duty. IP20 on the front protects against finger contact; IP00 at the terminals means the wiring area must be inside a closed panel. For a BOM line that needs this exact order code, the fit is confirmed by the AC-2 power rating and the screw-terminal main circuit — no rewiring or panel modification required if replacing an existing S2 contactor.","metaTitle":"Siemens SIRIUS 3RT1036-1AP60-0UA0 Power Contactor, S2, 22 kW","metaDescription":"Siemens SIRIUS 3RT1036-1AP60-0UA0 power contactor, size S2, rated 22 kW at 400 V AC-2, 30 kW at 500 V. Screw terminals, IP20 front. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"220 V","at 500 V rated value":"30 kW","at 60 Hz rated value":"240 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.6 VA","apparent pick-up power of magnet coil at AC":"166 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=536381&mlfb=3RT1036-1AP60-0UA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AP60-0UA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for this contactor?","answer":"It is rated 22 kW at 400 V AC-2, 30 kW at 500 V, and 11.4 kW at 690 V. These cover motor switching on 400 V and 690 V networks at both 50 Hz and 60 Hz."},{"question":"What conductor sizes does the screw terminal accept?","answer":"Solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded: 2x (0.75 to 25 mm²). Solid or stranded: 2x (0.75 to 16 mm²)."},{"question":"Can this contactor be mounted side-by-side with others?","answer":"Yes, side-by-side mounting is permitted. The IP20 front and IP00 terminals mean it's designed for enclosed panel installation with no additional spacing required between units."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AP60-0UA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AP60-0UA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}