{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1XF00-0GA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1XF00-0GA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1XF00-0GA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1XF00-0GA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1036-1XF00-0GA0, screw-type terminals, 500 V rated 30 kW at AC-3, 690 V rated 11.4 kW, 55 mm width, 130 mm depth, 142 mm height, IP20 front, DIN EN 50022 rail mount.","salesMarkdown":"It carries a 30 kW rating at 500 V in AC-3 duty, and 11.4 kW at 690 V — the AC-3 figure is the one that governs motor starts under load, so that 500 V, 30 kW line is what you size the contactor against for a standard induction motor. Main circuit terminals are screw-type, accepting solid wire from 2x 0.5 to 4 mm² and stranded up to 2x 25 mm². The front of the contactor is IP20 — finger-safe for panel access; the terminal area itself is IP00, meaning the wiring zone is open and needs enclosure protection against dust and accidental contact. Coil pickup at 50 Hz is 0.8 to 1.1 times rated voltage; dropout on DC takes 20 to 25 ms. Shock resistance is 15 g for 5 ms and 8 g for 10 ms on AC — enough for panel-mounted gear in conveyor or pump stations that see vibration from adjacent machinery. ## Switching frequency and auxiliary ratings Maximum switching rates: 1000 ops/h for AC-1 resistive loads, 800 ops/h for AC-3 motor duty, 400 ops/h for AC-2, and 300 ops/h for AC-4 reversing duty. The auxiliary contact ratings cover 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V — these are the values for the built-in auxiliary block, so verify your control voltage against the curve before wiring.","metaTitle":"Siemens 3RT1036-1XF00-0GA0 SIRIUS Power Contactor, Size S2","metaDescription":"Siemens 3RT1036-1XF00-0GA0 SIRIUS power contactor, size S2. Rated 500V 30kW AC-3, 690V 11.4kW. Screw terminals, DIN rail mount. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"15g / 5 ms, 8g / 10 ms","at DC":"20 ... 25 ms","Height":"142 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Design Of The Surge Suppressor":"with varistor","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"18.5 VA","apparent pick-up power of magnet coil at AC":"12.5 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.79","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=536353&mlfb=3RT1036-1XF00-0GA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1XF00-0GA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1036-1XF00-0GA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3RT1036-1XF00-0GA0's listed depth?","answer":"The depth is 130 mm, with a width of 55 mm and height of 142 mm."},{"question":"What wire sizes does the 3RT1036-1XF00-0GA0 accept?","answer":"Solid wire: 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², max 2x 0.75 to 4 mm². Stranded: 2x 0.75 to 25 mm². Also accepts 2x 0.75 to 16 mm² for solid or stranded."},{"question":"Will 3RT1036-1XF00-0GA0 drop into a panel specified for 3RT1044-1FB46 without rewiring?","answer":"No — the 3RT1044-1FB46 is a different frame size with different ratings and terminal layout. This 3RT1036 is a size S2; the 3RT1044 is a larger frame. Panel cutouts, DIN rail position, and wiring distances differ. Verify the physical footprint and terminal assignments before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1XF00-0GA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1XF00-0GA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}