{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1XP00-0GA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1XP00-0GA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1XP00-0GA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1XP00-0GA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, S2 size, 3RT1036-1XP00-0GA0, 55 mm width, screw-type terminals, 22 kW AC-2 at 400 V, 30 kW at 500 V, 10 A at 24 V auxiliary contacts.","salesMarkdown":"## SIRIUS S2 Power Contactor — Panel Integration Note Rated for AC-2 duty at 22 kW at 400 V and AC-4 at 41 A at 400 V, this contactor handles reversing and inching applications where the load current is interrupted under full motor current. For AC-3 duty, the 30 kW rating at 500 V covers standard squirrel-cage motor starting. Operating temperature range is -25 to +60 °C, with storage from -55 to +80 °C, and pollution degree 3 suits industrial environments with conductive contamination. Maximum switching frequency varies by duty: 1,000 cycles/hour at AC-1, 800 at AC-3, 400 at AC-2, and 300 at AC-4 — the AC-4 figure governs frequent plugging or jogging applications. Solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded conductors: 2x (0.75 to 25 mm²). Solid or stranded: 2x (0.75 to 16 mm²). These ranges cover standard panel wiring from control circuits to motor feeders. Auxiliary contacts are rated: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V. These cover typical PLC input signals, relay coils, and indicator lamps across common control voltages.","metaTitle":"Siemens 3RT1036-1XP00-0GA0 SIRIUS Power Contactor, S2, 55mm","metaDescription":"Siemens SIRIUS power contactor 3RT1036-1XP00-0GA0, S2 size, 55mm width, screw terminals, 22 kW AC-2 at 400V, 30 kW at 500V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"15g / 5 ms, 8g / 10 ms","at DC":"20 ... 25 ms","Height":"142 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Design Of The Surge Suppressor":"with varistor","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"18.5 VA","apparent pick-up power of magnet coil at AC":"12.5 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.79","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=25596&mlfb=3RT1036-1XP00-0GA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1XP00-0GA0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for 3RT1036-1XP00-0GA0?","answer":"As a Siemens SIRIUS product, standard documentation includes the manufacturer's declaration of conformity to applicable EU directives, RoHS and REACH compliance statements, and UL/CSA certification data. Specific certificates are available upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1XP00-0GA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1XP00-0GA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}