{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-3AF06","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-3AF06","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-3AF06","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-3AF06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1036-3AF06, Size S2 power contactor, 22 kW AC-2 at 400 V, 41 A AC-4 at 400 V, screw-type terminals, DIN rail mount, IP20 front.","salesMarkdown":"## SIRIUS 3RT1036-3AF06 — Power Contactor for Motor Loads It is rated for 22 kW in AC-2 duty at 400 V — the category for slip-ring motor starting and reversing — and delivers 41 A in AC-4 duty at 400 V, covering plugging and inching applications. The 30 kW rating at 500 V (AC-3) and 11.4 kW at 690 V (AC-3) extend its reach to higher-voltage motor circuits common in European and export panels. The main power circuit uses screw-type terminals, accepting 2x (0.75...25 mm²) stranded or 2x (0.25...2.5 mm²) solid conductors — a wide clamping range that simplifies wiring to both motor cables and control wiring. The 3RT1036-3AF06 is rated for 30 kW at 500 V in AC-3, which covers most 400/480 V three-phase motors in that power band. AC-4 at 400 V (41 A) is the more severe duty for reversing or jogging, where the contactor breaks stalled-rotor current. The contactor is rated for 10 million mechanical operations typical, with electrical endurance varying by duty: up to 1,000,000 cycles at AC-1 (resistive), 800,000 at AC-3, and 300,000 at AC-4. Substance prohibition date is 05/01/2012. Dimensions are 75 mm wide, 112 mm high, and 115 mm deep — a Size S2 footprint that fits standard 35 mm DIN rail.","metaTitle":"Siemens 3RT1036-3AF06 SIRIUS Power Contactor, 22 kW AC-2 at","metaDescription":"Siemens SIRIUS 3RT1036-3AF06 power contactor, Size S2, 22 kW AC-2 at 400 V, 41 A AC-4 at 400 V. Screw terminals, DIN rail mount. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"75 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"12.5 VA","apparent pick-up power of magnet coil at AC":"145 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.79","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=459126&mlfb=3RT1036-3AF06","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-3AF06/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to the 3RT1036-3AF06?","answer":"The 3RT1036-1AB00 is a peer in the same Size S2 frame, but it has a different coil voltage or terminal configuration. Verify coil rating and auxiliary block compatibility before substituting directly."},{"question":"Can the 3RT1036-3AF06 be mounted side-by-side without derating?","answer":"Yes, side-by-side mounting is permitted without derating, allowing multiple contactors to be ganged on the same DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-3AF06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-3AF06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}