{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1054-1SF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1054-1SF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1054-1SF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1054-1SF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S6, 3RT1054-1SF36, 96-127 VAC 50/60 Hz coil, screw-type terminals, rated for AC-1/AC-3/AC-4 switching.","salesMarkdown":"The coil is rated 96-127 VAC at 50/60 Hz with screw-type terminals, and the main power circuit accepts stranded conductors from 16 to 70 mm². The contactor is fastened by screw fixing to a vertical mounting surface, rotatable ±90° and tiltable ±22.5°. Switching rates: 750 operations per hour for AC-1 and AC-3 duty, 400 for AC-2, and 130 for AC-4. The arcing time is 10-15 ms, and the mechanical life is typically 10,000,000 operations. MTBF is listed at 75 years. ## Sizing and integration Dimensions: 172 mm height, 120 mm width, 170 mm depth. The auxiliary switch is included (screw-type terminals). The contactor is designed for panel mounting with screw fixing, typical for SIRIUS S6 frame installations in motor control centers. ## Switching performance AC-1 maximum current at 750 ops/h for resistive loads. AC-3 motor switching at 750 ops/h. AC-4 (plugging/reversing) at 130 ops/h. The coil pick-up is 0.8 x rated voltage (76.8 V minimum), drop-out at 0.6 x rated voltage (57.6 V). Operate time 115-130 ms AC and DC; release time 115-130 ms. Auxiliary contact ratings: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V.","metaTitle":"Siemens 3RT1054-1SF36 SIRIUS Power Contactor, 96-127 VAC Coi","metaDescription":"Siemens SIRIUS power contactor 3RT1054-1SF36, size S6, 96-127 VAC 50/60 Hz coil, screw terminals. MTBF 75 a. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"MTBF":"75 a","Depth":"170 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"120 mm","at AC":"115 ... 130 ms","at DC":"115 ... 130 ms","title":"3RT1054-1SF36","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"16 ... 70 mm²","at 50 Hz":"0.6","at 60 Hz":"0.6","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"96 ... 127 V","description":"power contactor, AC-3e/AC-3 115 A, 55 kW / 400 V, AC (50-60 Hz) / DC Uc: 96-127 V x (0.8-1.1) F-PLC input 24 V DC 3-pole, auxiliary contacts 2 NO + 2 NC drive: electronic main circuit: box terminal control and auxiliary circuit: screw terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"750 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"750 1/h","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"25 hp","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"124 A","at 50 Hz rated value":"96 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"96 ... 127 V","at 600 V rated value":"125 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"75 kW","For Auxiliary Contacts":"18 ... 14","For Main Current Circuit":"box terminal","at 200/208 V rated value":"40 hp","at 220/230 V rated value":"50 hp","at 460/480 V rated value":"100 hp","at 575/600 V rated value":"125 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Safe failure fraction (SFF)":"93 %","Safety-Related Switching On":"No","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"21 W","at AC-2 at 400 V rated value":"55 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"97 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"03/01/2017","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"140 A","at AC-5b up to 400 V rated value":"95 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)","Without Load Current Share Typical":"2.8 W","closing power of magnet coil at DC":"320 W","holding power of magnet coil at DC":"2.8 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","category according to EN ISO 13849-1":"2","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"7 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","stop category according to EN 60204-1":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","voltage at PLC-control input rated value":"24 V","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Recovery Time After Power Failure Typical":"2 s","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"16 ... 70 mm²","safety device type according to IEC 61508-2":"Type B","Type Of Voltage Of The Control Supply Voltage":"AC/DC","hardware fault tolerance according to IEC 61508":"0","Limited To 1 S Switching At Zero Current Maximum":"2 565 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 654 A; Use minimum cross-section acc. to AC-1 rated value","PFHD with high demand rate according to EN 62061":"4.5E-7 1/h","Limited To 10 S Switching At Zero Current Maximum":"1 170 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"729 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"572 A; Use minimum cross-section acc. to AC-1 rated value","SIL Claim Limit (subsystem) according to EN 62061":"2","PFDavg with low demand rate according to IEC 61508":"0.007","performance level (PL) according to EN ISO 13849-1":"c","type of PLC-control input according to IEC 60947-1":"Type 1","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","operating range factor of the voltage at PLC-control input":"0.8 ... 1.1","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"70 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$247.65","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=907582&mlfb=3RT1054-1SF36"},"ai":{"faq":[{"question":"What is the MTBF of 3RT1054-1SF36?","answer":"The listed MTBF is 75 years."},{"question":"Where can I buy 3RT1054-1SF36?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What wire sizes does 3RT1054-1SF36 accept?","answer":"Main power circuit accepts stranded 16-70 mm². Auxiliary terminals accept 2x 0.5-1.5 mm² solid, 2x 0.75-2.5 mm² stranded, max 2x 0.75-4 mm²."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1054-1SF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1054-1SF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}