{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1054-1XJ46-0LA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1054-1XJ46-0LA2","canonicalUrl":"https://aoctrl.com/siemens/3RT1054-1XJ46-0LA2","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1054-1XJ46-0LA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, size S6, 6 main contacts, DC coil 72 V, screw fixing, 170 x 120 x 172 mm.","salesMarkdown":"It carries six main contacts and includes an auxiliary switch, so it handles both power and feedback in one package. The DC coil is rated at 72 V, with a pickup time of 80 to 90 ms and an arcing time of 10 to 15 ms — numbers you want when coordinating with upstream protection. The main terminals accept stranded cable up to 2x 70 mm², and the auxiliary terminals handle solid or stranded wire from 0.5 to 4 mm². One 9 mm hole is provided for mounting. ## Duty cycles and ratings Maximum switching frequency varies by duty: 800 operations per hour at AC-1 (resistive), 1 000 at AC-3 (standard motor starting), and 130 at AC-4 (plugging/inching). For DC loads, it's 400/h at DC-1, 500/h at DC-3, and 500/h at DC-5. The auxiliary contacts are rated at 6 A at 24 V DC, 2 A at 48 V, and 2 A at 60 V.","metaTitle":"Siemens 3RT1054-1XJ46-0LA2 SIRIUS Contactor, Size S6, DC Coi","metaDescription":"Siemens SIRIUS contactor 3RT1054-1XJ46-0LA2, size S6, 6 main contacts, DC coil 72 V, screw fixing, current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"170 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"120 mm","at DC":"80 ... 90 ms","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"max. 2x 70 mm²","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"72 V","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Number Of Holes":"1","Type Of Voltage":"DC","at AC-1 maximum":"800 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"130 1/h","at DC-1 maximum":"400 1/h","at DC-3 maximum":"500 1/h","at DC-5 maximum":"500 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +70 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.25","at AC-3e maximum":"1 000 1/h","Diameter Of Holes":"9 mm","For Main Contacts":"6","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"25 hp","at 400 V rated value":"3 A","at 480 V rated value":"124 A","at 500 V rated value":"2 A","at 600 V rated value":"125 A","at 690 V rated value":"48 kW","Design Of The Product":"With extended operating range","Instantaneous Contact":"2","Side-By-Side Mounting":"Yes","at 1000 V rated value":"75 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"17 mm","For Main Current Circuit":"screw-type terminals","at 200/208 V rated value":"40 hp","at 220/230 V rated value":"50 hp","at 460/480 V rated value":"100 hp","at 575/600 V rated value":"125 hp","at AC-2 at AC-3e maximum":"400 1/h","Relative Humidity Minimum":"10 %","at maximum Ith rated value":"70 mm²","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"3 mm","at AC-3 rated value maximum":"1 000 V","at maximum AC-1 rated value":"70 mm²","at AC in hot operating state":"21 W","at AC-2 at 400 V rated value":"55 kW","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"97 A","Substance Prohibitance (Date)":"09/06/2016","Design Of The Surge Suppressor":"with varistor","at AWG cables for main contacts":"2x 1/0","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)","Without Load Current Share Typical":"2.8 W","closing power of magnet coil at DC":"320 W","holding power of magnet coil at DC":"2.8 W","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"7 W","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","voltage at PLC-control input rated value":"24 V","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"max. 1x 50, 1x 70 mm²","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"DC","up to 40 °C according to IEC 60077 rated value":"160 A","up to 70 °C according to IEC 60077 rated value":"120 A","Limited To 1 S Switching At Zero Current Maximum":"2 565 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 654 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 170 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"729 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"572 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=725718&mlfb=3RT1054-1XJ46-0LA2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1054-1XJ46-0LA2/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1054-1XJ46-0LA2?","answer":"The depth is 170 mm."},{"question":"What conductor sizes does the auxiliary terminal accept?","answer":"The auxiliary terminals accept solid or stranded wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²)."},{"question":"Where can I buy 3RT1054-1XJ46-0LA2?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1054-1XJ46-0LA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1054-1XJ46-0LA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}