{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1054-6AF36-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1054-6AF36-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1054-6AF36-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1054-6AF36-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S6, screw fixing, 110-127 VAC coil, 172 x 120 x 170 mm, auxiliary switch included, current production.","salesMarkdown":"The main power terminals accept stranded cable from 25 to 120 mm², which covers most motor feeders up to the S6 frame rating. Mounting is by screw fixing with a single 9 mm hole. The enclosure footprint is 172 mm high by 120 mm wide by 170 mm deep. ## Switching Performance and Duty Ratings The contactor is rated for AC-3 duty (motor switching) at up to 1000 operating cycles per hour, and for AC-3e at the same rate. For heavy-duty AC-4 (inching, plugging) the maximum is 130 cycles per hour. AC-1 (resistive) allows 800 cycles per hour, and AC-2 (slip-ring motor) allows 400 cycles per hour. These ratings define the thermal and mechanical limits for repetitive switching — a buyer specifying a high-cycle conveyor or crane application should match the duty class to the actual load profile. The auxiliary contact ratings are 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, and 1 A at 110 V. The coil pickup factor is 0.8 x rated voltage and 1.1 x rated voltage — meaning the coil will pick up reliably at 88 VAC on a 110 VAC system, and will hold in at 139.7 VAC on a 127 VAC system.","metaTitle":"Siemens 3RT1054-6AF36-ZX95 SIRIUS Power Contactor, S6, 110-1","metaDescription":"Siemens SIRIUS 3RT1054-6AF36-ZX95 power contactor, size S6, screw fixing, 110-127 VAC coil, 172x120x170 mm. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"170 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"120 mm","at AC":"40 ... 60 ms","at DC":"40 ... 60 ms","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"25 ... 120 mm²","at 50 Hz":"0.8","at 60 Hz":"0.8","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"110 ... 127 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"800 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"1 000 1/h","Diameter Of Holes":"9 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"25 hp","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"124 A","at 50 Hz rated value":"110 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"110 ... 127 V","at 600 V rated value":"125 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"75 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"17 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"40 hp","at 220/230 V rated value":"50 hp","at 460/480 V rated value":"100 hp","at 575/600 V rated value":"125 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"3 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"21 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"97 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","at AWG cables for main contacts":"4 ... 250 kcmil","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"140 A","at AC-5b up to 400 V rated value":"95 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)","Without Load Current Share Typical":"5.2 W","closing power of magnet coil at DC":"360 W","holding power of magnet coil at DC":"5.2 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"7 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"2 565 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 654 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 170 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"729 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"572 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"70 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=153336&mlfb=3RT1054-6AF36-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1054-6AF36-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of 3RT1054-6AF36-ZX95?","answer":"Height 172 mm, width 120 mm, depth 170 mm. Clearance requirements: 10 mm upwards, 10 mm downwards, 10 mm at the side, 20 mm forwards."},{"question":"What wire sizes does 3RT1054-6AF36-ZX95 accept?","answer":"The main power terminals accept stranded cable from 25 to 120 mm². The auxiliary/coil terminals accept solid or stranded wire: 2x (0.5-1.5 mm²), 2x (0.75-2.5 mm²), max 2x (0.75-4 mm²)."},{"question":"How do I get current pricing and availability for 3RT1054-6AF36-ZX95?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1054-6AF36-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1054-6AF36-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}