{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1054-6AS36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1054-6AS36","canonicalUrl":"https://aoctrl.com/siemens/3RT1054-6AS36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1054-6AS36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, 3RT1054-6AS36, Size S6, 120 mm width, 172 mm height, 170 mm depth, screw fixing, screw-type coil terminals.","salesMarkdown":"Maximum mechanical switching frequency under AC-3 duty is 1 000 operations per hour, matching the AC-3e rating. For AC-1 resistive loads the limit is 800 operations per hour, while AC-4 (plugging / inching) drops to 130 operations per hour. The arcing time is specified at 10 to 15 ms. The auxiliary switch is included as standard. Physical envelope: 120 mm wide, 172 mm tall, 170 mm deep. The contactor mounts via screw fixing, with four 9 mm diameter mounting holes. These clearances must be maintained for proper arc quenching and heat dissipation.","metaTitle":"Siemens SIRIUS 3RT1054-6AS36 Power Contactor, Size S6, 120 m","metaDescription":"Siemens SIRIUS 3RT1054-6AS36 power contactor, Size S6, 120 mm wide, 172 mm tall, 170 mm deep. Screw fixing, screw-type coil terminals. Rated operating range -25 to +60 °C. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"170 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"120 mm","at AC":"40 ... 60 ms","at DC":"40 ... 60 ms","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"25 ... 120 mm²","at 50 Hz":"0.8","at 60 Hz":"0.8","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"500 ... 550 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"800 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"1 000 1/h","Diameter Of Holes":"9 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"25 hp","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"124 A","at 50 Hz rated value":"500 ... 550 V","at 500 V rated value":"2 A","at 60 Hz rated value":"500 ... 550 V","at 600 V rated value":"125 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"75 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"17 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"40 hp","at 220/230 V rated value":"50 hp","at 460/480 V rated value":"100 hp","at 575/600 V rated value":"125 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"3 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"21 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"97 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","at AWG cables for main contacts":"4 ... 250 kcmil","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"140 A","at AC-5b up to 400 V rated value":"95 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA)","Without Load Current Share Typical":"5.2 W","closing power of magnet coil at DC":"360 W","holding power of magnet coil at DC":"5.2 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"7 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"2 565 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 654 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 170 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"729 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"572 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"70 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=452871&mlfb=3RT1054-6AS36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1054-6AS36/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT1054-6AS36?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution, and availability with current pricing is confirmed at quote time."},{"question":"What is the closest functional second-source for 3RT1054-6AS36?","answer":"The peer 3RT1055-6QF35 is a Size S6 contactor in the same SIRIUS family. The deciding difference is the coil rating and auxiliary configuration — verify the coil voltage and auxiliary contact arrangement against your BOM before substituting."},{"question":"What are the physical dimensions of 3RT1054-6AS36?","answer":"Width 120 mm, height 172 mm, depth 170 mm. Mounting via screw fixing with four 9 mm holes. Minimum clearance: 10 mm up/down/sides, 20 mm forward."},{"question":"What compliance documentation does Siemens provide for 3RT1054-6AS36?","answer":"As a SIRIUS series product, it is designed to meet applicable IEC and UL standards for industrial control equipment. Specific declarations (RoHS, REACH, UL file) are available from Siemens upon request or via their support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1054-6AS36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1054-6AS36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}