{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1055-2AD36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1055-2AD36","canonicalUrl":"https://aoctrl.com/siemens/3RT1055-2AD36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1055-2AD36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S6, 42-48 V AC/DC coil, screw fixing, 25-120 mm² main circuit conductors, auxiliary switch included.","salesMarkdown":"## Siemens SIRIUS 3RT1055-2AD36 — Power Contactor, Size S6 It carries a 42-48 V AC/DC coil (rated value 42-48 V) and includes an auxiliary switch (auxiliary switch yes). The main circuit accepts stranded conductors from 25 to 120 mm² (stranded 25-120 mm²), while the auxiliary circuit takes solid or stranded 2x 0.25-2.5 mm² (solid 2x 0.25-2.5 mm²). Coil termination uses spring-type terminals (of magnet coil spring-type terminals). Fastened via screw fixing (fastening method screw fixing) through a single 9 mm hole (number of holes 1, diameter of holes 9 mm). Mounting position allows vertical surface with +/-90° rotation and +/-22.5° tilt forward/backward (mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/-22.5° tiltable to the front and back). Dimensions: width 120 mm, height 172 mm, depth 170 mm (width 120 mm, height 172 mm, depth 170 mm). Clearance distances: upwards 10 mm, downwards 10 mm, forwards 20 mm, at the side 10 mm (upwards 10 mm, downwards 10 mm, forwards 20 mm, at the side 10 mm). ## Switching Performance and Endurance Rated for AC-1 maximum 800 operations per hour (at AC-1 maximum 800 1/h), AC-2 maximum 300 ops/h (at AC-2 maximum 300 1/h), AC-3 maximum 750 ops/h (at AC-3 maximum 750 1/h), AC-3e maximum 750 ops/h (at AC-3e maximum 750 1/h), and AC-4 maximum 130 ops/h (at AC-4 maximum 130 1/h). Arcing time is 10-15 ms (arcing time 10-15 ms). Mechanical endurance typical 10,000,000 operations (of contactor typical 10,000,000). Auxiliary contact ratings: 10 A at 24 V rated value (at 24 V rated value 10 A), 2 A at 48 V (at 48 V rated value 2 A), 2 A at 60 V (at 60 V rated value 2 A), 1 A at 110 V (at 110 V rated value 1 A).","metaTitle":"Siemens 3RT1055-2AD36 SIRIUS Power Contactor, 42-48 V Coil,","metaDescription":"Siemens SIRIUS power contactor 3RT1055-2AD36, size S6, 42-48 V AC/DC coil, 25-120 mm² main conductors. Current lifecycle stage. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"170 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"120 mm","at AC":"40 ... 60 ms","at DC":"40 ... 60 ms","title":"3RT1055-2AD36","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"25 ... 120 mm²","at 50 Hz":"0.8","at 60 Hz":"0.8","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"42 ... 48 V","description":"power contactor, AC-3e/AC-3 150 A, 75 kW / 400 V AC (50-60 Hz) / DC Uc: 42-48 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: spring-loaded terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","Number Of Holes":"1","at AC-1 maximum":"800 1/h","at AC-2 maximum":"300 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"750 1/h","Diameter Of Holes":"9 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,25 ... 2,5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"30 hp","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"156 A","at 50 Hz rated value":"42 ... 48 V","at 500 V rated value":"2 A","at 60 Hz rated value":"42 ... 48 V","at 600 V rated value":"144 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"90 kW","For Auxiliary Contacts":"24 ... 14","Width Of Connection Bar":"17 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"50 hp","at 220/230 V rated value":"60 hp","at 460/480 V rated value":"125 hp","at 575/600 V rated value":"150 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"3 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"27 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"132 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","at AWG cables for main contacts":"4 ... 250 kcmil","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"162 A","at AC-5b up to 400 V rated value":"124 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA)","Without Load Current Share Typical":"5.2 W","closing power of magnet coil at DC":"360 W","holding power of magnet coil at DC":"5.2 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"9 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"2 727 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 831 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 300 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"850 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"703 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"95 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=173822&mlfb=3RT1055-2AD36"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RT1055-2AD36?","answer":"The peer 3RT1055-6QF35 is a similar SIRIUS size S6 contactor, but it uses a 36-42 V coil versus the 42-48 V coil on the 3RT1055-2AD36 — verify coil voltage compatibility before substituting."},{"question":"What are the key dimensions of 3RT1055-2AD36?","answer":"Width 120 mm, height 172 mm, depth 170 mm."},{"question":"What conductor sizes does 3RT1055-2AD36 accept?","answer":"Main circuit accepts stranded 25-120 mm²; auxiliary circuit accepts solid or stranded 2x 0.25-2.5 mm²."},{"question":"Where can I buy 3RT1055-2AD36?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution — availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1055-2AD36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1055-2AD36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}