{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1055-6AP36-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1055-6AP36-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1055-6AP36-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1055-6AP36-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S6 power contactor, 3RT1055-6AP36-ZX95, 220-240 VAC coil, screw-type terminals, 25-120 mm² main circuit, size S6.","salesMarkdown":"The main power circuit accepts stranded conductors from 25 mm² up to 120 mm², which covers motor feeds up to about 55 kW at 400 V (rough rule — verify against your motor FLA). Switching frequency depends on duty: AC-1 (resistive) at 800 ops/h, AC-3 (squirrel-cage motor start/run) at 750 ops/h, AC-4 (plugging/inching) at 130 ops/h. The AC-3e rating mirrors the AC-3 figure at 750 ops/h. For a conveyor line cycling every 30 seconds, that's well within the AC-3 ceiling; for a press brake doing rapid reversals, you'll want to stay under the AC-4 limit. Auxiliary contacts are present — the built-in switch block is rated 10 A at 24 V, 2 A at 48 V and 60 V, and 1 A at 110 V. This contactor uses screw fixing (bolt-through), not DIN-rail snap-on. Mounting surface must be vertical, with ±90° rotation allowed and ±22.5° tilt forward/back. That gives flexibility for tight enclosures, but it's not a DIN-rail part — budget for a backplate and drilled holes. Footprint: 172 mm high, 120 mm wide, 170 mm deep. That's a substantial block — size S6. Clearance requirements: 10 mm above and below, 20 mm in front, 10 mm to the sides. A standard 600x600 mm enclosure can hold a few of these side by side, but watch the depth if the panel door has a deep component (like a disconnect handle) behind the contactor. ## Wiring and terminations Main power terminals accept stranded 25-120 mm² — that's a single large conductor or two smaller ones. The auxiliary circuit terminals are screw-type as well, accepting 2x (0.5-1.5 mm²) solid or 2x (0.75-2.5 mm²) stranded, max 2x (0.75-4 mm²). Use ferrules on stranded auxiliary wires to avoid strand spread under the screw. Operating delay is 40-60 ms on both AC and DC coil pickup — consistent, not unusually fast. Arcing time is 10-15 ms, which is typical for this frame size. For the coil, the rated value of 0.8 power factor at 50/60 Hz means the inrush current is moderate; the initial value is also 0.8. No suppression built in — add a varistor or RC snubber across the coil if driving from a PLC output.","metaTitle":"Siemens 3RT1055-6AP36-ZX95 SIRIUS Power Contactor, 220-240 V","metaDescription":"Siemens SIRIUS S6 power contactor, 220-240 VAC coil. Rated for AC-3 switching at 750 ops/h. Screw-type coil terminals, 25-120 mm² main conductors. Current production. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"170 mm","Width":"120 mm","Height":"172 mm","Mounting":"screw fixing","Arcing Time":"10 ... 15 ms","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=83990&mlfb=3RT1055-6AP36-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1055-6AP36-ZX95/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1055-6AP36-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1055-6AP36-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}