{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1055-6NP36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1055-6NP36","canonicalUrl":"https://aoctrl.com/siemens/3RT1055-6NP36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1055-6NP36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S6, 3RT1055-6NP36, 200-277 V AC coil, screw-type terminals, depth 170 mm.","salesMarkdown":"The coil pulls in on 200–277 V AC. Mechanical switching life is listed at 10 million operations typical, which puts it in the heavy-duty range for a contactor this size — expect it to outlast the machine it's in on cyclic loads like conveyors or pumps. The contactor is rated for AC-3 maximum switching frequency of 750 operations per hour, and AC-4 at 130 operations per hour. Mounting is screw fixing, not DIN rail snap-on. The contactor size S6 is physically large (172 mm high, 120 mm wide, 170 mm deep) — you're bolting this to a backplate, not clipping it onto a rail. That's tight for a part this size; plan your enclosure depth accordingly. The mounting position allows vertical surface mounting with ±90° rotation or ±22.5° tilt front-to-back, so panel layout isn't locked to one orientation. Main power circuit terminals accept stranded wire from 25 mm² up to 120 mm² — that's a heavy lug range, consistent with a size S6 contactor rated for high current. That gives flexibility for daisy-chaining control power or feedback loops without extra terminal blocks.","metaTitle":"Siemens 3RT1055-6NP36 SIRIUS Power Contactor, S6, 200-277 V","metaDescription":"Siemens SIRIUS 3RT1055-6NP36 power contactor, size S6, 200-277 V AC coil, screw terminals. Current lifecycle stage. Depth 170 mm. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"170 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"120 mm","at AC":"80 ... 90 ms","at DC":"80 ... 90 ms","title":"3RT1055-6NP36","Height":"172 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"25 ... 120 mm²","at 50 Hz":"0.6","at 60 Hz":"0.6","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"200 ... 277 V","description":"power contactor, AC-3e/AC-3 150 A, 75 kW / 400 V AC (50-60 Hz) / DC Uc: 200-277 V PLC input 24 V DC 3-pole, auxiliary contacts 2 NO + 2 NC drive: electronic main circuit: busbar control and auxiliary circuit: screw terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"800 1/h","at AC-2 maximum":"300 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"750 1/h","Diameter Of Holes":"9 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S6","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"30 hp","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"156 A","at 50 Hz rated value":"200 ... 277 V","at 500 V rated value":"2 A","at 60 Hz rated value":"200 ... 277 V","at 600 V rated value":"144 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"90 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"17 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"50 hp","at 220/230 V rated value":"60 hp","at 460/480 V rated value":"125 hp","at 575/600 V rated value":"150 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"3 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"27 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"132 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"162 A","at AC-5b up to 400 V rated value":"124 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA)","Without Load Current Share Typical":"2.8 W","closing power of magnet coil at DC":"320 W","holding power of magnet coil at DC":"2.8 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 355 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"9 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","voltage at PLC-control input rated value":"24 V","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"2 727 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"1 831 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"1 300 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"850 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"703 A; Use minimum cross-section acc. to AC-1 rated value","type of PLC-control input according to IEC 60947-1":"Type 2","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","operating range factor of the voltage at PLC-control input":"0.8 ... 1.1","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"95 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$274.32","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48191814343ef1de12d436857500061f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=145465&mlfb=3RT1055-6NP36"},"ai":{"faq":[{"question":"What is the closest functional second-source — 3RT1055-6AU36?","answer":"The 3RT1055-6AU36 is a peer variant in the same SIRIUS size S6 family. The key difference is the coil voltage: the 3RT1055-6NP36 uses a 200–277 V AC coil, while the 3RT1055-6AU36 uses a different coil voltage. They share the same physical footprint and terminal layout, so panel fit is identical, but the control circuit voltage must match."},{"question":"What is the depth of this contactor?","answer":"The depth is 170 mm."},{"question":"What wire sizes does the control circuit accept?","answer":"The control circuit terminals accept solid or stranded wire: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), and max 2x (0.75–4 mm²)."},{"question":"Will 3RT1055-6NP36 drop into a panel specified for 3RT1055-6AU36 without rewiring?","answer":"Yes, the physical dimensions and mounting are identical between the two (same S6 frame, same screw fixing, same clearance requirements). The only difference is the coil voltage — if the panel's control circuit is 200–277 V AC, it drops in without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1055-6NP36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1055-6NP36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}