{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1064-2NF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1064-2NF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1064-2NF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1064-2NF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, Size S10, 3RT1064-2NF36, 96-127 VAC coil, spring-type coil terminals, screw fixing, 210 x 145 x 202 mm.","salesMarkdown":"## SIRIUS Size S10 Power Contactor for Motor Loads The 96-127 VAC coil pulls in reliably down to 80% of rated voltage, and the contactor handles the full AC-3 duty cycle for squirrel-cage motors. Spring-type terminals on the coil save a few seconds per connection compared to screw terminals — a small thing until you've wired a hundred of them in a MCC lineup. ## Ratings That Matter for the Panel Builder AC-3 switching at up to 500 operations per hour is the number that governs motor starting duty — this contactor cycles a motor start every 7 seconds without exceeding thermal limits. AC-4 at 130 ops/h covers plugging and inching applications where the contactor breaks full locked-rotor current. The mechanical life of 10 million typical operations means this part outlasts the panel it lives in for most conveyor and pump cycles. Power cable termination accepts 70 to 240 mm² stranded copper. Auxiliary terminals take 2x 0.25 to 2.5 mm² solid or stranded. Auxiliary switch is built in. Operate time is 80 to 100 ms on both AC and DC supplies, and arcing time runs 10 to 15 ms. That consistency matters for coordination studies — the fault clearance window is tight enough to keep downstream fuses from nuisance-blowing on a motor start. ## Mounting and Clearance for the Enclosure Layout Screw fixing through a single 11 mm hole secures the contactor to the back panel. The 210 x 145 x 202 mm envelope (H x W x D) fits a standard MCC bucket depth. ## Environmental Range and Lifecycle","metaTitle":"Siemens 3RT1064-2NF36 SIRIUS Power Contactor, Size S10, 96-1","metaDescription":"Siemens 3RT1064-2NF36 SIRIUS power contactor, Size S10 frame, 96-127 VAC coil, spring-type terminals. Rated for AC-3 motor switching. Current lifecycle stage. Available to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"145 mm","at AC":"80 ... 100 ms","at DC":"80 ... 100 ms","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.4","at 60 Hz":"0.4","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"96 ... 127 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","Number Of Holes":"1","at AC-1 maximum":"750 1/h","at AC-2 maximum":"250 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"500 1/h","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,25 ... 2,5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"180 A","at 50 Hz rated value":"96 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"96 ... 127 V","at 600 V rated value":"192 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"90 kW","For Auxiliary Contacts":"24 ... 14","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"60 hp","at 220/230 V rated value":"75 hp","at 460/480 V rated value":"150 hp","at 575/600 V rated value":"200 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"51 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"195 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"242 A","at AC-5b up to 400 V rated value":"186 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)","Without Load Current Share Typical":"3.4 W","closing power of magnet coil at DC":"580 W","holding power of magnet coil at DC":"3.4 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"17 W","for AWG cables for auxiliary contacts":"2x (24 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","voltage at PLC-control input rated value":"24 V","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"4 000 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"2 807 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"2 082 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"1 397 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"1 144 A; Use minimum cross-section acc. to AC-1 rated value","type of PLC-control input according to IEC 60947-1":"Type 2","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","operating range factor of the voltage at PLC-control input":"0.8 ... 1.1","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"150 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6b047d8a3667b9c5998178fdb4a2004.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=440467&mlfb=3RT1064-2NF36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1064-2NF36/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3RT1064-2NF36?","answer":"AC-3 switching at up to 500 ops/h, AC-4 at 130 ops/h, mechanical life of 10 million typical operations, power cable termination 70-240 mm² stranded, coil 96-127 VAC with spring-type terminals, and operating temperature -25 to +60 °C."},{"question":"What compliance documentation does Siemens provide for 3RT1064-2NF36?","answer":"As a SIRIUS power contactor, this part is covered by Siemens' standard CE declaration of conformity and UL/CSA certifications for the series. Specific document numbers are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1064-2NF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1064-2NF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}