{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1064-6AP36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1064-6AP36","canonicalUrl":"https://aoctrl.com/siemens/3RT1064-6AP36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1064-6AP36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S10, 220-240 V AC coil, screw-type terminals, 70-240 mm² stranded main circuit, auxiliary switch included.","salesMarkdown":"## SIRIUS Power Contactor, Size S10 The coil is rated for 220-240 V AC (cites:,). Main circuit wiring accepts stranded conductors from 70 to 240 mm², while the control circuit uses screw-type terminals accepting 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), or max. 2x (0.75... 4 mm²) solid or stranded (cites:,). An auxiliary switch is included, rated at 24 V for 10 A, 48 V for 2 A, 60 V for 2 A, and 110 V for 1 A (cites:,). ## Switching Performance and Duty Ratings Maximum switching rates vary by duty: 750 operations per hour at AC-1 (resistive), 250 at AC-2, 500 at AC-3 and AC-3e, and 130 at AC-4 (cites:,). The AC-3 and AC-3e rates are the relevant figures for standard squirrel-cage motor starting — 500 ops/h covers most conveyor and pump cycling without derating (cites:,). Coil pickup is guaranteed at 0.8 x rated voltage; dropout occurs at 1.1 x rated value (cites:,). ## Mounting and Environmental Fastening is by screw fixing with a single 11 mm diameter mounting hole (cites:,). Dimensions are 210 mm height, 145 mm width, and 202 mm depth (cites:,).","metaTitle":"Siemens 3RT1064-6AP36 SIRIUS Power Contactor, Size S10, 220-","metaDescription":"Siemens 3RT1064-6AP36 SIRIUS power contactor, size S10, 220-240 V AC coil, screw terminals, rated for 70-240 mm² stranded. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"145 mm","at AC":"40 ... 80 ms","at DC":"40 ... 80 ms","title":"3RT1064-6AP36","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.9","at 60 Hz":"0.9","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"220 ... 240 V","description":"power contactor, AC-3e/AC-3 225 A, 110 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"750 1/h","at AC-2 maximum":"250 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"500 1/h","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"180 A","at 50 Hz rated value":"220 ... 240 V","at 500 V rated value":"2 A","at 60 Hz rated value":"220 ... 240 V","at 600 V rated value":"192 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"90 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"60 hp","at 220/230 V rated value":"75 hp","at 460/480 V rated value":"150 hp","at 575/600 V rated value":"200 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"51 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"195 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"242 A","at AC-5b up to 400 V rated value":"186 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)","Without Load Current Share Typical":"7.4 W","closing power of magnet coil at DC":"650 W","holding power of magnet coil at DC":"7.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"17 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"4 000 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"2 807 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"2 082 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"1 397 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"1 144 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"150 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$341.63","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8c6fe0351bfceed5c3a82b39309216df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=213967&mlfb=3RT1064-6AP36"},"ai":{"faq":[{"question":"What are the main circuit wiring specifications for 3RT1064-6AP36?","answer":"The main circuit accepts stranded conductors from 70 to 240 mm². The control circuit uses screw-type terminals accepting 2x (0.5... 1.5 mm²), 2x (0.75... 2.5 mm²), or max. 2x (0.75... 4 mm²) solid or stranded (cites:,)."},{"question":"What is the depth of 3RT1064-6AP36?","answer":"The depth is 202 mm (cite:). Overall dimensions are 210 mm height, 145 mm width, and 202 mm depth (cites:,)."},{"question":"Where can I buy 3RT1064-6AP36?","answer":"This part is available to order through independent distribution. Submit an RFQ for current pricing and availability — the part is sourced to order against confirmed requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1064-6AP36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1064-6AP36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}