{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1064-6AP36-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1064-6AP36-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1064-6AP36-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1064-6AP36-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S10, 220-240 V 50 Hz coil, screw-type terminals, 202 mm depth.","salesMarkdown":"The 220-240 V 50 Hz coil pulls in reliably with an operating range of 0.8 to 1.1 times rated voltage at 50 Hz — meaning it picks up at about 176 V and holds in through line sags down to that same threshold. Dropout is around 0.8 times initial value, so below roughly 176 V the contactor opens cleanly. For motor duty, the contactor is rated at 160 kW at 500 V — that's the AC-3 switching capability for a three-phase induction motor. The auxiliary contact block handles 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V, so it can drive small relays or PLC inputs directly. Mounts via screw fixing — four 11 mm holes on the base plate. That 20 mm forward gap is the one that catches people out when the panel door or a busbar shroud is tight. The coil uses screw-type terminals, so no special crimp tool needed for the control wiring. Main power terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) — that's two conductors per clamp, which is handy for daisy-chaining line or load side without extra terminal blocks. Strip length and torque follow standard Siemens practice for this frame size. ## Environmental and switching performance Switching frequency: 750 cycles/hour max under AC-1 resistive load, 500 cycles/hour under AC-3 motor load, and 130 cycles/hour under AC-4 plugging/reversing duty.","metaTitle":"Siemens SIRIUS 3RT1064-6AP36-1AA0 Power Contactor, S10, 220-","metaDescription":"Siemens SIRIUS power contactor 3RT1064-6AP36-1AA0, size S10, 220-240 V 50 Hz coil, screw terminals. Active production. Sourced to order. Depth 202 mm.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"145 mm","at AC":"40 ... 80 ms","at DC":"40 ... 80 ms","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.8 ... 1.1","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"220 ... 240 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"750 1/h","at AC-2 maximum":"250 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"500 1/h","Diameter Of Holes":"11 mm","Size Of Contactor":"S10","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"220 ... 240 V","at 500 V rated value":"160 kW","at 60 Hz rated value":"220 ... 240 V","at 690 V rated value":"82 kW","Side-By-Side Mounting":"Yes","at 1000 V rated value":"90 kW","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","Relative Humidity Minimum":"10 %","Thickness Of Connection Bar":"6 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"51 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"195 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","at AC-5a up to 690 V rated value":"242 A","at AC-5b up to 400 V rated value":"186 A","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)","Without Load Current Share Typical":"7.4 W","closing power of magnet coil at DC":"650 W","holding power of magnet coil at DC":"7.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"17 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"4 000 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"2 807 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"2 082 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"1 397 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"1 144 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"150 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=221361&mlfb=3RT1064-6AP36-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1064-6AP36-1AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"Coil is 220-240 V 50 Hz. Motor power rating is 160 kW at 500 V (AC-3). Auxiliary contacts handle 10 A at 24 V, 6 A at 230 V, 3 A at 400 V. Mechanical life is 10 million operations. Dimensions: 210 mm high, 145 mm wide, 202 mm deep."},{"question":"Will 3RT1064-6AP36-1AA0 drop into a panel specified around 3RT5065-6AB36?","answer":"No — the 3RT1064 is a size S10 frame (210 x 145 x 202 mm) while the 3RT5065 is a different frame size. Mounting hole pattern and terminal spacing differ; rewiring and re-drilling the mounting plate would be required."},{"question":"What conductor sizes does the main terminal accept?","answer":"Two conductors per clamp: 0.5 to 1.5 mm², 0.75 to 2.5 mm², or up to 0.75 to 4 mm² — all solid or stranded."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1064-6AP36-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1064-6AP36-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}