{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1065-6AF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1065-6AF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1065-6AF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1065-6AF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S10, 3RT1065-6AF36, 110-127 VAC coil, screw-type terminals, auxiliary switch included.","salesMarkdown":"## SIRIUS S10 Power Contactor — 3RT1065-6AF36 Its magnet coil is rated for 110-127 V AC and terminates on screw-type terminals, with an integrated auxiliary switch for feedback or interlocking. Rated mechanical life is 10 million operations typical, and the contactor is rated for up to 500 operations per hour in AC-3 duty (motor switching) and 800 ops/hr in AC-1 (resistive). The contactor occupies 145 mm width, 210 mm height, and 202 mm depth — a compact footprint for the S10 current class. ## Coil and Auxiliary Contact Ratings The coil pulls in at 80% of rated voltage. Operate time is 40-80 ms on both AC and DC supplies; arcing time is 10-15 ms. Main power poles accept stranded conductors from 70 to 240 mm², sized for the S10 frame's current capacity. The coil and auxiliary terminals accept solid or stranded wire: 2x 0.5-1.5 mm², 2x 0.75-2.5 mm², or max 2x 0.75-4 mm². Screw fixing with an 11 mm mounting hole diameter suits standard panel backplates.","metaTitle":"Siemens 3RT1065-6AF36 SIRIUS Power Contactor, Size S10, 110-","metaDescription":"Siemens 3RT1065-6AF36 SIRIUS power contactor, Size S10 frame, 110-127 VAC coil, screw terminals. Rated for motor switching up to AC-3 duty. Available to order; request quote for cu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"145 mm","at AC":"40 ... 80 ms","at DC":"40 ... 80 ms","title":"3RT1065-6AF36","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.9","at 60 Hz":"0.9","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"110 ... 127 V","description":"power contactor, AC-3e/AC-3 265 A, 132 kW / 400 V AC (50-60 Hz) / DC Uc: 110-127 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"800 1/h","at AC-2 maximum":"250 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"500 1/h","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"240 A","at 50 Hz rated value":"110 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"110 ... 127 V","at 600 V rated value":"242 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"132 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"75 hp","at 220/230 V rated value":"100 hp","at 460/480 V rated value":"200 hp","at 575/600 V rated value":"250 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"54 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"230 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"290 A","at AC-5b up to 400 V rated value":"219 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)","Without Load Current Share Typical":"7.4 W","closing power of magnet coil at DC":"650 W","holding power of magnet coil at DC":"7.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"18 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"4 880 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"4 045 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"2 785 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"1 664 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"1 276 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"185 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$469.90","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/52d697707cfd9d086b38133b838b62bc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=160903&mlfb=3RT1065-6AF36"},"ai":{"faq":[{"question":"What is 3RT1065-6AF36's listed depth?","answer":"The depth is 202 mm, with a width of 145 mm and height of 210 mm."},{"question":"What wire sizes does the coil terminal accept?","answer":"The coil and auxiliary terminals accept solid or stranded wire: 2x 0.5-1.5 mm², 2x 0.75-2.5 mm², or max 2x 0.75-4 mm²."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1065-6AF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1065-6AF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}