{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1066-6PP35","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1066-6PP35","canonicalUrl":"https://aoctrl.com/siemens/3RT1066-6PP35","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1066-6PP35","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1066-6PP35 power contactor, size S10, screw-type magnet coil terminals, 240 mm² stranded cable, 3-pole, 210 x 165 x 202 mm.","salesMarkdown":"## Panel fit: 210 x 165 x 202 mm The 3RT1066-6PP35: The contactor measures 210 mm high, 165 mm wide, and 202 mm deep — a substantial footprint that requires a backplate or DIN-rail adapter bracket (not included) with screw fixing through 11 mm holes. Mounting position is flexible: vertical surface with ±90° rotation, or ±22.5° tilt forward/back. ## Operating envelope and coil data Pickup/dropout delay is 80...100 ms for both AC and DC, arcing time 10...15 ms. The contactor includes an auxiliary switch (standard fit) and is rated for 10 million typical mechanical operations. ## Switching duty and lifecycles Maximum switching rates: 750 ops/h at AC-1 (resistive), 250 ops/h at AC-2, 500 ops/h at AC-3 and AC-3e (standard motor duty), and 130 ops/h at AC-4 (plugging/reversing). The AC-3/AC-3e rate of 500 ops/h is typical for conveyor and pump cycling.","metaTitle":"Siemens 3RT1066-6PP35 SIRIUS Power Contactor, S10, 240 mm²","metaDescription":"Siemens 3RT1066-6PP35 SIRIUS power contactor, size S10, screw terminals, 240 mm² cable. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"165 mm","at AC":"80 ... 100 ms","at DC":"80 ... 100 ms","title":"3RT1066-6PP35","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.4","at 60 Hz":"0.4","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"200 ... 277 V","description":"power contactor, AC-3e/AC-3 300 A, 160 kW / 400 V, AC (50-60 Hz) / DC Uc: 200-277 V PLC input 24 V DC 3-pole, auxiliary contacts 1 NO + 1 NC drive: electronic main circuit: busbar control and auxiliary circuit: screw terminal with remaining lifetime indicator","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","at AC-1 maximum":"750 1/h","at AC-2 maximum":"250 1/h","at AC-3 maximum":"500 1/h","at AC-4 maximum":"130 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","at AC-3e maximum":"500 1/h","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1.4 A","at 480 V rated value":"302 A","at 50 Hz rated value":"200 ... 277 V","at 500 V rated value":"2 A","at 60 Hz rated value":"200 ... 277 V","at 600 V rated value":"289 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","at 1000 V rated value":"132 kW","For Auxiliary Contacts":"18 ... 14","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","at 200/208 V rated value":"100 hp","at 220/230 V rated value":"125 hp","at 460/480 V rated value":"250 hp","at 575/600 V rated value":"300 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC-3 rated value maximum":"1 000 V","at AC in hot operating state":"66 W","at AC-3e rated value maximum":"1 000 V","at AC-4 at 400 V rated value":"280 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"290 A","at AC-5b up to 400 V rated value":"249 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)","Without Load Current Share Typical":"3.4 W","closing power of magnet coil at DC":"580 W","holding power of magnet coil at DC":"3.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"22 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","voltage at PLC-control input rated value":"24 V","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Limited To 1 S Switching At Zero Current Maximum":"5 524 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"4 579 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"3 153 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"1 883 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"1 445 A; Use minimum cross-section acc. to AC-1 rated value","type of PLC-control input according to IEC 60947-1":"Type 2","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","operating range factor of the voltage at PLC-control input":"0.8 ... 1.1","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","for short-circuit protection of the RLT relay output required":"miniature fuse: 4 A FF (230 V, Ik= 400 A)","minimum cross-section in main circuit at maximum AC-1 rated value":"185 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fbd72b45a391f601ff7911c221390878.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=204464&mlfb=3RT1066-6PP35"},"ai":{"faq":[{"question":"What is the main power cable size for the 3RT1066-6PP35?","answer":"The main poles accept stranded cable from 70 mm² up to 240 mm² — the largest in the SIRIUS contactor range, sized for high-current motor feeders or resistive loads."},{"question":"Does the 3RT1066-6PP35 include an auxiliary contact block?","answer":"Yes, the contactor comes with an auxiliary switch integrated as standard."},{"question":"Can the 3RT1066-6PP35 be mounted on a DIN rail?","answer":"No — the fastening method is screw fixing through 11 mm holes, not snap-on DIN rail. It requires a backplate or adapter bracket for panel installation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1066-6PP35","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1066-6PP35 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}