{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1276-6NF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1276-6NF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1276-6NF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1276-6NF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1276-6NF36 vacuum contactor, size S12, 3-pole, 225 mm depth, 214 mm height, 160 mm width, screw-type coil terminals, 96-127 V AC/DC coil.","salesMarkdown":"The 3RT1276-6NF36: This is a Siemens SIRIUS vacuum contactor in the S12 frame size — the vacuum bottle extinguishes the arc inside a sealed chamber, so the contact gap stays clean and the switching life holds up under high-cycle motor starting or furnace duty where an air-break contactor would pit the contacts after a few thousand operations. The physical envelope is 225 mm deep by 214 mm high by 160 mm wide — the depth is the dimension that usually bites you on a shallow backpanel or a retrofit into an existing enclosure where the gland plate or busbar trunking limits how far the contactor projects from the mounting surface. Coil voltage is 96 to 127 V AC/DC with screw-type terminals — the wide AC/DC tolerance means it holds in on a control transformer with a sagging secondary or a battery-backed DC bus, provided the initial pickup voltage stays above 0.8 × rated value and the full-scale overvoltage does not exceed 1.1 × rated. Main power cables land on terminals accepting 70 to 240 mm² stranded copper — that is a 4/0 AWG to 500 kcmil range, sized for the full rated current of the contactor without needing a separate lug adapter on the line or load side. ## Switching frequency and duty-cycle limits The contactor is rated for 750 operations per hour in AC-3 and AC-3e duty (squirrel-cage motor starting) and 700 ops/h in AC-1 (resistive load) — the vacuum bottle handles the arc without the thermal recovery delay that limits an air-break contactor, so the cycle rate is set by the magnet system heating, not the main contacts. In AC-2 (slip-ring motor starting) and AC-4 (plugging / inching) the rate drops to 250 ops/h — the longer arcing time during reversal heats the vacuum bottle envelope, and the manufacturer's rating assumes the contactor is not operated above this frequency without a duty-cycle derating.","metaTitle":"Siemens 3RT1276-6NF36 SIRIUS Vacuum Contactor, S12","metaDescription":"Siemens 3RT1276-6NF36 SIRIUS vacuum contactor, size S12, 225 mm depth, 214 mm height, 160 mm width. Coil 96-127 V AC/DC. Screw-type coil terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"225 mm","Width":"160 mm","Height":"214 mm","Mounting":"screw fixing","Arcing Time":"10 ... 15 ms","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4a912183ecbe25fdd30c0b4568e05c07.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=58457&mlfb=3RT1276-6NF36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1276-6NF36/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1276-6NF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1276-6NF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}