{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1317-1AB00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1317-1AB00","canonicalUrl":"https://aoctrl.com/siemens/3RT1317-1AB00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1317-1AB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 4 NO main contacts, 5.5 kW at 400 V AC-2, screw terminals, 45 mm width, active production.","salesMarkdown":"It is rated for motor switching at 5.5 kW at 400 V AC-2, and carries a maximum operating current of 10 A at AC-12. The enclosure is IP20 on the front and at the terminals, suitable for dry indoor panel environments. ## Ratings and coordination The main contacts handle 10 A in AC-12 resistive loads. For short-circuit protection, type 1 coordination requires a 35 A gL/gG fuse; type 2 coordination requires a 20 A gL/gG fuse. The coil is rated for 24 V at 50/60 Hz, with a tolerance of 0.8 to 1.1 times the rated voltage at 50 Hz, and 0.85 to 1.1 at 60 Hz.","metaTitle":"Siemens 3RT1317-1AB00 SIRIUS Power Contactor, 4 NO, 5.5 kW A","metaDescription":"Siemens SIRIUS power contactor, size S00, 4 NO main contacts, 5.5 kW at 400 V AC-2. Active production, screw terminals, 45 mm wide. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"24 V","at 60 Hz rated value":"24 V","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"4","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"4","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$22.31","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=404369&mlfb=3RT1317-1AB00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1317-1AB00/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for the 3RT1317-1AB00?","answer":"The 3RT1023-1AL20 is a peer contactor in the same SIRIUS family, but it has a different contact configuration and ratings. The 3RT1317-1AB00 has four NO main contacts and a 5.5 kW AC-2 rating, while the 3RT1023-1AL20 has three NO plus one NC and a different power rating. It will not drop into a panel wired for the 3RT1023-1AL20 without rewiring the main contacts."},{"question":"What is the depth of the 3RT1317-1AB00?","answer":"The depth is 72 mm."},{"question":"What wire sizes does the 3RT1317-1AB00 accept?","answer":"The screw terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max. 2x (0.75 to 4 mm²). For AWG, it accepts 2x (20 to 16), 2x (18 to 14), and 1x 12."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1317-1AB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1317-1AB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}