{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1317-1AD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1317-1AD00","canonicalUrl":"https://aoctrl.com/siemens/3RT1317-1AD00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1317-1AD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 4 NO main contacts, 5.5 kW at AC-2 400 V, screw terminals, 45 mm wide, IP20.","salesMarkdown":"## Integrator's first look The Siemens 3RT1317-1AD00 is a SIRIUS power contactor in the S00 frame size — the smallest footprint in the family at 45 mm wide, 57.5 mm high, and 72 mm deep. Screw-type terminals accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded, with a maximum of 2x (0.75 to 4 mm²). The 5.5 kW at AC-2 400 V rating is the motor-switching figure that governs real-world use — AC-2 covers slip-ring motors and other loads where the contactor makes and breaks at full load. For resistive loads (AC-1), the same contactor handles up to 10 A continuous. The 4 NO main contact arrangement means this contactor closes all four poles simultaneously; there are no NC main contacts on this variant. Short-circuit coordination is specified: Type 2 coordination requires a 20 A gL/gG fuse, while Type 1 allows a 35 A fuse — important for selectivity studies in the panel. Auxiliary contact ratings span 10 A at 24 V up to 0.3 A at 220 V, covering typical PLC and relay interface voltages. The contactor is approved for side-by-side mounting without derating, which saves panel space when multiple contactors are ganged. At 45 mm wide, this S00 contactor occupies a single 45 mm slot on a DIN rail. Screw terminals are clearly marked and accept ferruled conductors; strip length for the main circuit terminals is approximately 10 mm. The IP20 rating means the contactor is touch-safe out of the box — no additional terminal covers are needed for standard panel builds.","metaTitle":"Siemens 3RT1317-1AD00 SIRIUS Power Contactor, S00, 4 NO, 5.5","metaDescription":"Siemens 3RT1317-1AD00 SIRIUS power contactor, size S00, 4 NO main contacts, 5.5 kW at AC-2 400 V, screw terminals, 45 mm wide, IP20. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"42 V","at 60 Hz rated value":"42 V","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"4","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"4","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=465056&mlfb=3RT1317-1AD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1317-1AD00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the 3RT1317-1AD00?","answer":"It is a SIRIUS power contactor, size S00, with 4 NO main contacts. Motor switching rating is 5.5 kW at AC-2 400 V. Resistive load rating is 10 A at AC-1. Mechanical endurance is 30 million operations. Operating temperature range is -25 to +60 °C."},{"question":"What wire sizes does the 3RT1317-1AD00 accept?","answer":"Screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, and a maximum of 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."},{"question":"What is the mounting method for the 3RT1317-1AD00?","answer":"It mounts via screw or snap-on onto a 35 mm standard mounting rail per DIN EN 50022. Side-by-side mounting is permitted without derating."},{"question":"What short-circuit protection is required for the 3RT1317-1AD00?","answer":"For Type 2 coordination, use a 20 A gL/gG fuse. For Type 1 coordination, a 35 A gL/gG fuse is permitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1317-1AD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1317-1AD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}