{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1336-1AR60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1336-1AR60","canonicalUrl":"https://aoctrl.com/siemens/3RT1336-1AR60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1336-1AR60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1336-1AR60, screw-type terminals, 23 kW at 230 V AC-1, 11 kW at 400 V AC-2, DIN EN 50022 rail mount, IP20 front.","salesMarkdown":"It carries a 23 kW resistive rating at 230 V (AC-1) and an 11 kW motor rating at 400 V (AC-2) — the AC-2 figure is the one that governs for standard squirrel-cage motors on conveyor or pump duty, so size your motor branch circuit against that number, not the higher AC-1 value. The control circuit takes 0.5–1.5 mm² solid or 0.75–2.5 mm² stranded. Strip length and ferrule sizing follow standard practice — no oddball pitch here. The IP20 front enclosure keeps fingers off live parts inside the panel; the terminals themselves are IP00, meaning the panel enclosure provides the final touch protection.","metaTitle":"Siemens 3RT1336-1AR60 SIRIUS Power Contactor, 23 kW at 230 V","metaDescription":"Siemens 3RT1336-1AR60 SIRIUS power contactor, size S2. Rated 23 kW at 230 V AC-1, 11 kW at 400 V AC-2. Screw terminals, DIN rail mount. IP20 front. Current lifecycle stage. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"73 mm","at AC":"10 ... 30 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"400 ... 440 V","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"11 kW","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"23 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.6 VA","apparent pick-up power of magnet coil at AC":"166 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=34252&mlfb=3RT1336-1AR60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1336-1AR60/alternatives.json"},"ai":{"faq":[{"question":"What is the AC-2 motor rating of 3RT1336-1AR60?","answer":"The AC-2 motor rating is 11 kW at 400 V — that is the figure to use when sizing for standard induction motor loads."},{"question":"What is the depth of 3RT1336-1AR60?","answer":"The depth is 115 mm, with a width of 73 mm and height of 112 mm — fits standard DIN-rail enclosures without overhang."},{"question":"Where can I buy 3RT1336-1AR60?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1336-1AR60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1336-1AR60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}