{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1364-6AF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1364-6AF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1364-6AF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1364-6AF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1364-6AF36 contactor, size S10, AC coil 48-130 V, 2 N/O instantaneous auxiliary contacts, screw-type terminals, screw fixing.","salesMarkdown":"## What it is and key fit decisions The Siemens 3RT1364-6AF36 is a SIRIUS contactor in the S10 frame size, with an AC coil rated for 48 to 130 V at 50/60 Hz. The contactor is screw-fixed to the mounting surface, not snap-on DIN rail, so panel integration means drilling or tapping the backplate — account for that in the BOM if you're swapping from a DIN-rail style. Coil pick-up is guaranteed at 80% of rated voltage, and drop-out occurs at 110% of rated voltage — meaning this contactor holds in cleanly down to about 38.4 V on a 48 V nominal coil, and drops out if the control supply swells above about 143 V. That's a wide operating band, useful on lines with saggy or lightly regulated control transformers. Coil draw is 4 VA at both 50 and 60 Hz, which is modest for the S10 frame. Dimensions are 196 mm high, 140 mm wide, 153 mm deep. That depth is the body only — add for wiring space and finger clearance. The contactor can be mounted on a vertical surface, rotated ±180°, or tilted forward/backward up to 30° at 0° rotation. If you're packing this into a shallow enclosure, that forward clearance is the tightest constraint. ## Wiring and auxiliary contacts That's typical for control wiring up to 14 AWG. The two instantaneous N/O contacts are rated at 24 V / 3 A, 48 V / 1.5 A, 110-125 V / 0.55 A, 220 V / 0.3 A, 230 V / 4 A, 400 V / 3 A, 500 V / 2 A, and 690 V / 2 A. Note the 230 V and 400 V ratings are higher than the low-voltage ones — that's the AC-15 / utilization category curve at work; don't assume linear derating. Up to two additional auxiliary contact blocks can be attached to this contactor, giving flexibility to add more N/O or N/C contacts without a separate relay.","metaTitle":"Siemens 3RT1364-6AF36 SIRIUS Contactor, S10, AC Coil 48-130V","metaDescription":"Siemens 3RT1364-6AF36 SIRIUS contactor, size S10, AC coil 48-130V, 2 N/O instantaneous contacts, screw terminals. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"153 mm","Solid":"1x (1 ... 4mm²), 2x (1 ... 4mm²)","Width":"140 mm","at AC":"45 ... 80 ms","at DC":"45 ... 80 ms","Height":"196 mm","Upwards":"10 mm","Forwards":"20 mm","at 50 Hz":"4 VA","at 60 Hz":"4 VA","Downwards":"10 mm","Attachable":"2","At The Side":"10 mm","Rated Value":"48 ... 130 V","Initial Value":"0.8","During Storage":"-40 ... +70 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","Mounting Position":"For vertical mounting surface can be rotated +/-180°, and with 0° rotation can be tilted forward or backward +/- 30°, or standing","Size Of Contactor":"S10","Solid Or Stranded":"1x (1 ... 4mm²), 2x (1 ... 4mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"3 A","at 48 V rated value":"1.5 A","at 110 V rated value":"0.55 A","at 125 V rated value":"0.55 A","at 220 V rated value":"0.3 A","at 230 V rated value":"4 A","at 400 V rated value":"3 A","at 50 Hz rated value":"48 ... 130 V","at 500 V rated value":"2 A","at 60 Hz rated value":"48 ... 130 V","at 690 V rated value":"2 A","Instantaneous Contact":"2","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"18 ... 14","For Main Current Circuit":"Connection bar, broadened > 275A required","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","at AC in hot operating state":"100 W","at AC-3 at 400 V rated value":"110 kW","Substance Prohibitance (Date)":"03/27/2017","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (500 V, 100 kA)","Without Load Current Share Typical":"2.5 W","closing power of magnet coil at DC":"130 W","holding power of magnet coil at DC":"2.5 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","at AC in hot operating state per pole":"25 W","for AWG cables for auxiliary contacts":"1x (AWG 18 ... 14), 2x (AWG 18 ... 14)","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"1x (0.75 ... 2.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC/DC","contact rating of auxiliary contacts according to UL":"A600 / Q300","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"240 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1043711&mlfb=3RT1364-6AF36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1364-6AF36/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"Height is 196 mm, width is 140 mm, depth is 153 mm. Minimum clearances required: 10 mm upwards, 10 mm downwards, 10 mm at the side, and 20 mm forwards from the contactor body."},{"question":"What is the coil voltage and type?","answer":"The coil is AC type, rated for 48 to 130 V at both 50 and 60 Hz. Pick-up is guaranteed at 80% of rated voltage, drop-out at 110%."},{"question":"Does this contactor include auxiliary contacts?","answer":"Yes, it comes with two instantaneous normally-open auxiliary contacts. Up to two additional auxiliary contact blocks can be attached."},{"question":"What wire sizes does the terminal accept?","answer":"Each clamp accepts 1x (1 to 4 mm²) or 2x (1 to 4 mm²) solid or stranded conductors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1364-6AF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1364-6AF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}