{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1364-6AP36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1364-6AP36","canonicalUrl":"https://aoctrl.com/siemens/3RT1364-6AP36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1364-6AP36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, size S10, 3RT1364-6AP36, 100-250 V AC 50/60 Hz coil, screw-type terminals, auxiliary switch, 153 mm depth, 140 mm width, 196 mm height.","salesMarkdown":"## Mounting and clearance — fitting it into the enclosure The 3RT1364-6AP36: Clearance distances are 10 mm upwards, downwards, and to the side, and 20 mm forwards — these are the minimum air gaps to adjacent metalwork or other devices to avoid arc flash tracking and to allow heat dissipation from the coil. Overall dimensions are 196 mm height, 140 mm width, and 153 mm depth — the depth is the dimension that often catches panel builders when the enclosure backplate is tight against the gland plate. ## Termination and auxiliary contacts An auxiliary switch is included as standard, with two instantaneous contacts (NO/NC configuration not specified in the record, but the presence of the switch means the contactor can signal its state back to the PLC or annunciator without an add-on block).","metaTitle":"Siemens 3RT1364-6AP36 SIRIUS Contactor, 100-250 V AC Coil","metaDescription":"Siemens 3RT1364-6AP36 SIRIUS contactor, size S10, 100-250 V AC 50/60 Hz coil. Screw terminals, auxiliary switch included. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"153 mm","Solid":"1x (1 ... 4mm²), 2x (1 ... 4mm²)","Width":"140 mm","at AC":"45 ... 80 ms","at DC":"45 ... 80 ms","Height":"196 mm","Upwards":"10 mm","Forwards":"20 mm","at 50 Hz":"7 VA","at 60 Hz":"7 VA","Downwards":"10 mm","Attachable":"2","At The Side":"10 mm","Rated Value":"100 ... 250 V","Initial Value":"0.8","During Storage":"-40 ... +70 °C","Of Magnet Coil":"Screw-type terminals","Type Of Voltage":"AC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-40 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","Mounting Position":"For vertical mounting surface can be rotated +/-180°, and with 0° rotation can be tilted forward or backward +/- 30°, or standing","Size Of Contactor":"S10","Solid Or Stranded":"1x (1 ... 4mm²), 2x (1 ... 4mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"3 A","at 48 V rated value":"1.5 A","at 110 V rated value":"0.55 A","at 125 V rated value":"0.55 A","at 220 V rated value":"0.3 A","at 230 V rated value":"4 A","at 400 V rated value":"3 A","at 50 Hz rated value":"100 ... 250 V","at 500 V rated value":"2 A","at 60 Hz rated value":"100 ... 250 V","at 690 V rated value":"2 A","Instantaneous Contact":"2","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"18 ... 14","For Main Current Circuit":"Connection bar, broadened > 275A required","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","at AC in hot operating state":"100 W","at AC-3 at 400 V rated value":"110 kW","Substance Prohibitance (Date)":"03/27/2017","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","Product Function Bus Communication":"No","With Type Of Assignment 2 Required":"gG: 400 A (500 V, 100 kA)","Without Load Current Share Typical":"2.5 W","closing power of magnet coil at DC":"190 W","holding power of magnet coil at DC":"2.5 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","at AWG cables for auxiliary contacts":"1x (AWG 18 ... 14), 2x (AWG 18 ... 14)","at AC in hot operating state per pole":"25 W","number of NO contacts for main contacts":"4","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"1x (0.75 ... 2.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC/DC","contact rating of auxiliary contacts according to UL":"A600 / Q300","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (690 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"240 mm²","Of The Auxiliary And Control Circuit With Degree Of Pollution 3 Rated Value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7eae5e88eac02a0e5f61aa27cf768a17.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1043712&mlfb=3RT1364-6AP36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1364-6AP36/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1364-6AP36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1364-6AP36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}