{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1466-6NF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1466-6NF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1466-6NF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1466-6NF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, size S10, order code 3RT1466-6NF36, rated control voltage 96-127 V AC/DC, screw-type coil terminals, 4 attachable auxiliary switches, 202 mm depth.","salesMarkdown":"## SIRIUS S10 contactor, 96–127 V AC/DC coil The Siemens 3RT1466-6NF36 is a SIRIUS-branded contactor in frame size S10, designed for motor switching and general load control in industrial panels. Its coil accepts 96–127 V AC/DC, with a pick-up threshold of 0.8 x rated value and a full-scale hold of 1.1 x rated value. Operating time is 80–100 ms on both AC and DC; arcing time runs 10–15 ms. Mounts via screw fixing with one 11 mm hole. Overall dimensions are 210 mm height x 145 mm width x 202 mm depth. ## Wiring and auxiliary capacity Main power circuit accepts stranded conductors from 70 to 240 mm². The coil uses screw-type terminals accepting solid conductors: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), max 2x (0.75–4 mm²). The contactor ships with an auxiliary switch block and supports up to 4 attachable auxiliary switches. Switching capacity on the auxiliary contacts varies by voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 6 A at 230 V (–).","metaTitle":"Siemens 3RT1466-6NF36 SIRIUS Contactor, Size S10, 96-127 V A","metaDescription":"Siemens 3RT1466-6NF36 SIRIUS contactor, size S10, rated control voltage 96-127 V AC/DC. Screw-type coil terminals, 4 attachable auxiliary switches. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"145 mm","at AC":"80 ... 100 ms","at DC":"80 ... 100 ms","title":"3RT1466-6NF36","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.5","at 60 Hz":"0.8 ... 1.1","Downwards":"10 mm","Attachable":"4","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"96 ... 127 V","description":"power contactor AC-1 400 A / 690 V / 40 °C 3-pole, Uc: 96-127 V AC(50-60 Hz) / DC PLC input 24 V DC drive: electronic auxiliary contacts 2 NO + 2 NC main circuit: busbar control and auxiliary circuit: screw terminal","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","Type Of Voltage":"AC/DC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"96 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"96 ... 127 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"2","Side-By-Side Mounting":"Yes","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC in hot operating state":"105.6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gR: 500 A (690 V, 100 kA)","Without Load Current Share Typical":"3.4 W","closing power of magnet coil at DC":"580 W","holding power of magnet coil at DC":"3.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"600 1/h","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"35.2 W","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Type Of Voltage For Main Current Circuit":"AC","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC/DC","type of PLC-control input according to IEC 60947-1":"Type 2","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"240 mm²","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dcd3aad2e48b02d9ddda6447d1675b18.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=265805&mlfb=3RT1466-6NF36"},"ai":{"faq":[{"question":"What is the rated control voltage for 3RT1466-6NF36?","answer":"The rated control voltage is 96–127 V AC/DC. The coil picks up at 0.8 x rated value and holds at 1.1 x rated value."},{"question":"What are the mounting clearances for this contactor?","answer":"Minimum clearances: 10 mm upwards, 10 mm downwards, 10 mm at the side, and 20 mm forwards. Mounting is via screw fixing with one 11 mm hole."},{"question":"How many auxiliary switches can be attached to 3RT1466-6NF36?","answer":"The contactor supports up to 4 attachable auxiliary switches and ships with an auxiliary switch block included."},{"question":"Where can I buy 3RT1466-6NF36 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1466-6NF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1466-6NF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}