{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1466-6SF36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1466-6SF36","canonicalUrl":"https://aoctrl.com/siemens/3RT1466-6SF36","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1466-6SF36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS contactor, Size S10, 3RT1466-6SF36, coil 96-127 V AC/DC, screw-type terminals, MTBF 75 a.","salesMarkdown":"## SIRIUS S10 Contactor, 96-127 V AC/DC Coil The Siemens 3RT1466-6SF36 is a SIRIUS-brand Size S10 contactor with a 96-127 V AC/DC magnet coil terminated at screw-type terminals. The coil pick-up is 0.8 of rated value; drop-out below that threshold. Arcing time runs 10-15 ms across both AC and DC switching. Fastening via screw fixing through an 11 mm hole. The S10 frame accepts up to four auxiliary switch blocks. ## Power Circuit and Auxiliary Ratings Main power terminals accept stranded cable 70-240 mm². Auxiliary contact wiring: solid or stranded 2x (0.5-1.5 mm²), 2x (0.75-2.5 mm²), max 2x (0.75-4 mm²). Auxiliary switch present as standard. Rated operational current on auxiliary contacts: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V. The contactor is rated for 50/60 Hz operation with a power factor of 0.5 at 50 Hz and 0.8-1.1 at 60 Hz. The 3RT1466-6SF36 carries a current-production lifecycle status.","metaTitle":"Siemens 3RT1466-6SF36 SIRIUS Contactor, 96-127 V AC/DC Coil,","metaDescription":"Siemens 3RT1466-6SF36 SIRIUS contactor, Size S10, coil 96-127 V AC/DC, MTBF 75 a. Current-production part sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"MTBF":"75 a","Depth":"202 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"145 mm","at AC":"115 ... 130 ms","at DC":"115 ... 130 ms","Height":"210 mm","Upwards":"10 mm","Forwards":"20 mm","Stranded":"70 ... 240 mm²","at 50 Hz":"0.5","at 60 Hz":"0.8 ... 1.1","Downwards":"10 mm","Attachable":"4","Arcing Time":"10 ... 15 ms","At The Side":"10 mm","Rated Value":"96 ... 127 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","Number Of Holes":"1","Type Of Voltage":"AC/DC","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw fixing","Full-Scale Value":"1.1","Diameter Of Holes":"11 mm","Mounting Position":"with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back","Size Of Contactor":"S10","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"96 ... 127 V","at 500 V rated value":"2 A","at 60 Hz rated value":"96 ... 127 V","at 600 V rated value":"0.1 A","at 690 V rated value":"1 A","Instantaneous Contact":"2","Side-By-Side Mounting":"Yes","Width Of Connection Bar":"25 mm","For Main Current Circuit":"Connection bar","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"8 kV","Thickness Of Connection Bar":"6 mm","at AC in hot operating state":"105.6 W","Substance Prohibitance (Date)":"03/01/2017","Design Of The Surge Suppressor":"with varistor","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gR: 500 A (690 V, 100 kA)","Without Load Current Share Typical":"3.4 W","closing power of magnet coil at DC":"580 W","holding power of magnet coil at DC":"3.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","operating frequency at AC-1 maximum":"200 1/h","With Type Of Coordination 1 Required":"gG: 500 A (690 V, 100 kA)","category according to EN ISO 13849-1":"2","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"35.2 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","stop category according to EN 60204-1":"0","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Type Of Voltage For Main Current Circuit":"AC","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Product Function Short Circuit Protection":"No","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","safety device type according to IEC 61508-2":"Type B","with high demand rate according to SN 31920":"73 %","number of NC contacts for auxiliary contacts":"2","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC/DC","hardware fault tolerance according to IEC 61508":"0","PFHD with high demand rate according to EN 62061":"4.5E-7 1/h","SIL Claim Limit (subsystem) according to EN 62061":"2","PFDavg with low demand rate according to IEC 61508":"0.007","performance level (PL) according to EN ISO 13849-1":"c","type of PLC-control input according to IEC 60947-1":"Type 1","Of Main Circuit With Degree Of Pollution 3 Rated Value":"1 000 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"500 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"240 mm²","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","Design Of The Miniature Circuit Breaker For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (230 V, 400 A)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dcd3aad2e48b02d9ddda6447d1675b18.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=907622&mlfb=3RT1466-6SF36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1466-6SF36/alternatives.json"},"ai":{"faq":[{"question":"What is 3RT1466-6SF36's listed MTBF?","answer":"The mean time between failures (MTBF) for this contactor is 75 a."},{"question":"What is the coil voltage for 3RT1466-6SF36?","answer":"The coil is rated 96-127 V AC/DC with screw-type terminals."},{"question":"Where can I buy 3RT1466-6SF36?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Contact us for current pricing and availability at quote time."},{"question":"What compliance documentation does Siemens provide for 3RT1466-6SF36?","answer":"As a current-production SIRIUS contactor, standard Siemens documentation includes RoHS and REACH declarations; UL and IEC certifications are typically available. Specific certificate references should be confirmed at order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1466-6SF36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1466-6SF36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}