{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1517-1AR60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1517-1AR60","canonicalUrl":"https://aoctrl.com/siemens/3RT1517-1AR60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1517-1AR60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1517-1AR60, 24 VAC/DC coil, screw terminals, 45 mm width, IP20 front.","salesMarkdown":"## SIRIUS 3RT1517-1AR60 — 24 VAC/DC Power Contactor, Size S00 This contactor's rated operational current varies with the load voltage: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. The AC-1 maximum switching frequency is 1 000 operations per hour, with an arcing time of 10–15 ms and total operating time of 4–30 ms. For motor switching duty (AC-3), the per-contact rating is 12 A for both NO and NC auxiliary contacts. ## Coil and Environmental Ratings The coil draws 5.1 VA at 50 Hz and has a power factor of 0.27 at 60 Hz. It operates on a 50 Hz rated voltage of 400 V or a 60 Hz range of 400–440 V. The front face and terminals carry IP20 protection; altitude limit is 2 000 m. Mounting orientation allows ±180° rotation and ±30° tilt on a vertical surface. Screw terminals accept 2x 0.5–1.5 mm² solid, 2x 0.75–2.5 mm², or max 2x 0.75–4 mm². The Size S00 footprint (45 × 57.5 × 72 mm) fits standard control panel cutouts.","metaTitle":"Siemens 3RT1517-1AR60 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens 3RT1517-1AR60 SIRIUS power contactor, Size S00, 45 mm wide, 24 VAC/DC coil. Rated 10 A at 24 V, 6 A at 230 V, 3 A at 400 V. Screw terminals, IP20 front. Active production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","at AC":"4 ... 30 ms","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"5.1 V·A","at 60 Hz":"0.27","Arcing time":"10 ... 15 ms","At The Side":"6 mm","On The Front":"IP20","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-55 ... +80 °C","Of The Terminal":"IP20","at AC-1 maximum":"1 000 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Mounting position":"with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back","Size of contactor":"S00","Product brand name":"SIRIUS","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"0.8 A","at 50 Hz rated value":"400 V","at 60 Hz rated value":"400 ... 440 V","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","per NC contact rated value":"12 A","per NO contact rated value":"12 A","Of Main Circuit Rated Value":"6 kV","at maximum AC-1 rated value":"2.5 mm²","Of Auxiliary Circuit Rated Value":"6 kV","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at 24 V per NC contact rated value":"20 A","at 24 V per NO contact rated value":"20 A","at AC at 230 V maximum permissible":"0.003 A","Protection against electrical shock":"finger-safe","at 110 V per NC contact rated value":"0.175 A","at 110 V per NO contact rated value":"0.35 A","at 220 V per NC contact rated value":"0.375 A","at 220 V per NO contact rated value":"0.75 A","at 230 V per NC contact rated value":"3 kW","at 230 V per NO contact rated value":"3 kW","at 400 V per NC contact rated value":"5.5 kW","at 400 V per NO contact rated value":"5.5 kW","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"2","Number of NO contacts for main contacts":"2","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"4","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000","Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor":"0.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=214532&mlfb=3RT1517-1AR60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1517-1AR60/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of the 3RT1517-1AR60?","answer":"The 3RT1517-1AR60 has a depth of 72 mm."},{"question":"What wire sizes does the 3RT1517-1AR60 accept?","answer":"The screw terminals accept 2x (0.5–1.5 mm²) solid, 2x (0.75–2.5 mm²) solid, and max 2x (0.75–4 mm²) solid or stranded conductors."},{"question":"Will the 3RT1517-1AR60 drop into a panel wired for a 3RT1016-1AR11?","answer":"Yes, the 3RT1517-1AR60 shares the same Size S00 footprint (45 mm width) and DIN rail mounting as the 3RT1016-1AR11, so it fits the same panel cutout and rail. However, the 3RT1517-1AR60 has a higher rated current (12 A vs. 9 A at 400 V AC-3), so verify that the existing wiring and upstream protection are sized for the higher load."},{"question":"Where can I buy the 3RT1517-1AR60 and how is it quoted?","answer":"The 3RT1517-1AR60 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability; a firm quote is provided at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1517-1AR60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1517-1AR60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}