{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1535-1AD20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1535-1AD20","canonicalUrl":"https://aoctrl.com/siemens/3RT1535-1AD20","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1535-1AD20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1535-1AD20, screw-type terminals for main and auxiliary circuits, 40 A rated per NO/NC contact, 24 VDC coil, snap-on mounting on 35 mm DIN rail.","salesMarkdown":"That 40 A figure governs the auxiliary contact chain, not the main poles — the main circuit's switching capacity is defined by voltage-specific curves: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 1 A at 440 V. So for a 400 V motor circuit, the contactor's real current limit is 3 A, not 40 A. The coil pulls 15 VA at 50 Hz and holds at 24 VDC; arcing time sits between 10 and 15 ms, which matters for coordination with upstream fuses or breakers. The vertical mounting surface can be rotated ±180° or tilted ±30° front-to-back, so panel layout constraints are manageable. Side-by-side mounting is allowed, which keeps the rail footprint tight. Wire entry accepts solid conductors from 0.5 to 4 mm² (2x per terminal) and stranded up to 25 mm² (2x). That stranded range covers typical motor feeder cables up to about 4 AWG. Compliance documentation — RoHS, REACH, and the manufacturer's declaration of conformity — is available with the shipment.","metaTitle":"Siemens 3RT1535-1AD20 SIRIUS Power Contactor, S2, 40 A, 24 V","metaDescription":"Siemens SIRIUS 3RT1535-1AD20 power contactor, size S2, 40 A rated per NO/NC, 24 VDC coil, screw terminals, DIN rail mount. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"73 mm","at AC":"10 ... 30 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"15 VA","at 60 Hz":"0.35","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Mounting Position":"with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back","Size Of Contactor":"S2","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 440 V rated value":"1 A","at 50 Hz rated value":"42 V","at 60 Hz rated value":"42 V","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","per NC contact rated value":"40 A","per NO contact rated value":"40 A","Of Main Circuit Rated Value":"6 kV","Substance Prohibitance (Date)":"05/01/2012","at AWG cables for main contacts":"2x (18 ... 2)","Of Auxiliary Circuit Rated Value":"6 kV","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","at 24 V per NC contact rated value":"50 A","at 24 V per NO contact rated value":"50 A","at AC at 230 V maximum permissible":"0.018 A","At Contactor For Auxiliary Contacts":"Screw-type terminals","at 110 V per NC contact rated value":"12.5 A","at 110 V per NO contact rated value":"25 A","at 220 V per NC contact rated value":"2.5 A","at 220 V per NO contact rated value":"5 A","at 230 V per NC contact rated value":"9.5 kW","at 230 V per NO contact rated value":"9.5 kW","at 400 V per NC contact rated value":"18.5 kW","at 400 V per NO contact rated value":"18.5 kW","at 440 V per NC contact rated value":"0.135 A","at 440 V per NO contact rated value":"0.27 A","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"2","number of NO contacts for main contacts":"2","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"4","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"60 A","at ambient temperature 60 °C rated value":"55 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"15 VA","apparent pick-up power of magnet coil at AC":"170 VA","Type Of Voltage Of The Control Supply Voltage":"AC","for 3-phase AC motor at 460/480 V rated value":"25 hp","Inductive Power Factor With Closing Power Of The Coil":"0.76","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.35","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","minimum cross-section in main circuit at maximum AC-1 rated value":"16 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000","power loss [W] at AC-3 at 400 V for rated value of the operational current per conductor":"2.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=100835&mlfb=3RT1535-1AD20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1535-1AD20/alternatives.json"},"ai":{"faq":[{"question":"What solid conductor sizes does the 3RT1535-1AD20 accept?","answer":"It accepts 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²) solid conductors."},{"question":"What compliance documentation does Siemens provide for 3RT1535-1AD20?","answer":"RoHS compliance is confirmed by a substance prohibitance date of 05/01/2012; REACH and manufacturer declarations of conformity are available with the shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1535-1AD20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1535-1AD20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}