{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2015-1AK62-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2015-1AK62-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2015-1AK62-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2015-1AK62-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2015-1AK62-ZW96 power contactor, Size S00, 24 VDC coil, screw-type terminals, integrated auxiliary switch, current production.","salesMarkdown":"The contactor is rated for switching frequencies that depend on the duty class: up to 1,000 operations per hour in AC-1 (resistive) duty, 750 per hour in AC-2 and AC-3 (motor starting/running), and 250 per hour in AC-4 (plugging/inching). For a conveyor or pump running steady-state AC-3 duty, the 750 cycles/hour limit is the one that governs — it allows a cycle every 4.8 seconds, which covers most process rates without oversizing. The auxiliary contact ratings vary by voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.14 A at 440 V. For a 24 VDC PLC input, the 10 A rating is generous — the real limit is the PLC's own input current, not the contact. At 400 V, the 3 A rating is the one to check if you are switching a small control transformer or indicator lamp. That covers most indoor panel environments; if the panel is near a furnace or in a desert enclosure, the +60 °C upper limit is the hard stop. The contactor accepts solid or stranded wire from 0.5 to 4 mm², with dual-wire terminations possible: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². The coil terminals are screw-type, so a standard Pozidriv bit handles the connection. Clearance distances are 10 mm upwards, downwards, and forwards, 6 mm at the sides. That 6 mm side gap is the tightest constraint — adjacent devices need that breathing room for heat dissipation and wiring access. Main contact torque is specified at 20 to 12 (likely Nm, though the unit is truncated in the spec).","metaTitle":"Siemens 3RT2015-1AK62-ZW96 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT2015-1AK62-ZW96 power contactor, Size S00, 24 VDC coil, screw terminals. Current production. 45 mm wide, snaps onto DIN rail. Auxiliary switch included.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"7 ... 13 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.24","at 60 Hz":"0.24","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"0.75 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.14 A","at 480 V rated value":"4.8 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"6.1 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1.5 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.2 W","at AC-2 at 400 V rated value":"3 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"6.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"15.8 A","at AC-5b up to 400 V rated value":"5.8 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.4 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"120 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"67 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"52 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"43 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"2.5 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=753527&mlfb=3RT2015-1AK62-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2015-1AK62-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"The contactor is 45 mm wide, 58 mm high, and 73 mm deep. It requires 10 mm clearance upwards, downwards, and forwards, and 6 mm at the sides."},{"question":"What wire sizes does this contactor accept?","answer":"It accepts solid or stranded wire from 0.5 to 4 mm², and can terminate two wires per terminal in combinations like 2x 0.5-1.5 mm² or 2x 4 mm²."},{"question":"Does it include an auxiliary contact?","answer":"Yes, an auxiliary switch is built into the contactor, so no separate add-on block is required for basic signaling."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2015-1AK62-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2015-1AK62-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}