{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2015-1AK62-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2015-1AK62-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT2015-1AK62-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2015-1AK62-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT2015-1AK62-ZX95, size S00, 24 VDC coil, screw-type terminals, auxiliary switch included, DIN EN 60715 rail mount.","salesMarkdown":"At 24 V rated value, the main contacts carry 10 A, which is the continuous current for a resistive or lightly inductive load at that voltage. For motor duty (AC-3), the contactor is rated for 750 switching operations per hour maximum, and for AC-4 (plugging/reversing) that drops to 250 operations per hour — the contactor's mechanical life of 30 million operations is only achievable if you stay within these electrical switching limits. ## Termination and Wiring Considerations Screw-type terminals accept solid or stranded wire from 0.5 to 4 mm², and up to 2x 4 mm² or 2x (0.75 to 2.5 mm²) for paralleled conductors. The depth of 73 mm and width of 45 mm mean it fits standard S00 footprint cutouts, with minimum clearances of 10 mm upwards/downwards and 6 mm at the side for arc flash and heat dissipation.","metaTitle":"Siemens 3RT2015-1AK62-ZX95 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT2015-1AK62-ZX95 power contactor, size S00, 24 VDC coil, screw terminals, 10 A rated at 24 V. Current lifecycle stage. DIN rail mount. Sourced to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"7 ... 13 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.24","at 60 Hz":"0.24","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"0.75 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.14 A","at 480 V rated value":"4.8 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"6.1 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1.5 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.2 W","at AC-2 at 400 V rated value":"3 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"6.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"15.8 A","at AC-5b up to 400 V rated value":"5.8 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.4 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.4 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"120 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"67 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"52 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"43 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"2.5 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=753526&mlfb=3RT2015-1AK62-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2015-1AK62-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of this contactor?","answer":"The depth is 73 mm, which fits the standard S00 footprint for DIN-rail-mounted contactors."},{"question":"What wire sizes does the screw terminal accept?","answer":"Solid or stranded wire from 0.5 to 4 mm², and up to 2x 4 mm² or 2x (0.75 to 2.5 mm²) for paralleled conductors."},{"question":"Will the 3RT2015-1AK62-ZX95 drop into a panel specified for the 3RT2015-1AP02-ZX95?","answer":"The 3RT2015-1AP02-ZX95 is a peer MPN from the same SIRIUS S00 family. Both share the same mechanical footprint (45 mm width, 73 mm depth, DIN rail mount) and terminal wire ranges. The key difference is the coil voltage: the -1AK62 uses 24 VDC, while the -1AP02 uses a different coil voltage. Verify the coil voltage matches your control circuit before substituting."},{"question":"What compliance documentation is available for this part?","answer":"As a Siemens SIRIUS product, it carries CE marking for the European market and is designed to meet IEC/EN 60947-4-1 standards for contactors. Documentation typically includes a declaration of conformity and material data per RoHS and REACH. Specific certs (UL, CSA) depend on the exact variant; confirm with the order code's approval markings on the nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2015-1AK62-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2015-1AK62-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}