{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2015-2AV02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2015-2AV02","canonicalUrl":"https://aoctrl.com/siemens/3RT2015-2AV02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2015-2AV02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 24 V DC coil, spring-type terminals, screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715, auxiliary switch included.","salesMarkdown":"The coil is 24 V DC, rated at 10 A — that's the hold current at nominal voltage, not the switching current. Spring-type terminals on the magnet coil mean no tool needed for the control wiring; the main contacts use screw terminals accepting 0.5 to 4 mm² solid or stranded. ## Size S00 — what the footprint buys you At 45 mm wide, 70 mm tall, and 73 mm deep, this contactor fits the standard S00 envelope — the same footprint as the 3RT2015-2AP02 and -2AP01 siblings. The mounting position is flexible: +/-180° rotation on a vertical surface, and can be tilted forward/backward by +/-22.5° on vertical mounting, which helps in tight enclosures or angled gland plates. Clearance spacing is modest: 10 mm upwards and forwards, 10 mm downwards, 6 mm at the side. That keeps the panel fill factor reasonable even with several contactors ganged on the same DIN rail. ## Switching duty and auxiliary contact Rated for AC-1 (resistive) at 1,000 operations per hour maximum, AC-2 and AC-3 (motor starting) at 750 ops/h, and AC-4 (plugging/inching) at 250 ops/h. Arcing time runs 10 to 15 ms at AC, and the contactor's typical mechanical life is 30 million operations — that's the mechanical endurance, not the electrical life under load, which will be lower depending on the switching category. ## Environmental range and wiring Operates from -25 to +60 °C ambient; storage range is -55 to +80 °C. The main contact terminals accept 2x (0.5 to 4 mm²) solid or stranded — fine for panel wiring with standard ferrules.","metaTitle":"Siemens 3RT2015-2AV02 SIRIUS Power Contactor, Size S00, 24V","metaDescription":"Siemens 3RT2015-2AV02 SIRIUS power contactor, Size S00, spring-type terminals, 24V DC coil rated 10A, screw and snap-on DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"0.75 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.14 A","at 480 V rated value":"4.8 A","at 50 Hz rated value":"400 V","at 500 V rated value":"2 A","at 60 Hz rated value":"400 V","at 600 V rated value":"6.1 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1.5 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"0.6 W","at AC-2 at 400 V rated value":"3 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"6.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"15.8 A","at AC-5b up to 400 V rated value":"5.8 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.2 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.2 W","for AWG cables for auxiliary contacts":"2x (20 ... 12)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"120 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"67 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"52 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"43 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"2.5 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0842cdd8a639a1cb8d4a009eb514e3de.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=102581&mlfb=3RT2015-2AV02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2015-2AV02/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RT2015-2AV02?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What is the closest functional second-source to the 3RT2015-2AV02?","answer":"The 3RT2015-2AP02 is a close sibling — same Size S00 frame, same DIN rail mount, same spring-type coil terminals. The difference is the coil voltage: the -2AP02 uses a different AC/DC coil rating. Verify coil voltage compatibility before substituting."},{"question":"Will the 3RT2015-2AV02 drop into a panel specified for the 3RT2015-2AP02 without rewiring?","answer":"Yes, the mechanical footprint is identical — both are Size S00 with the same 45x70x73 mm envelope and DIN rail mounting. The main power wiring is interchangeable. The only difference is the coil voltage; rewire the control circuit if the coil ratings differ."},{"question":"What compliance documentation does Siemens provide for the 3RT2015-2AV02?","answer":"Siemens SIRIUS contactors typically carry UL, CSA, CE, and IEC certifications, and are RoHS and REACH compliant. Specific documentation (declarations of conformity, certificates) is available on request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2015-2AV02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2015-2AV02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}