{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2015-2FB41-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2015-2FB41-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT2015-2FB41-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2015-2FB41-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2015-2FB41-ZX95, contactor, AC-3, 3kW/400V, 1NO, DC 24V, with integrated diode, 3-pole, size S00, spring-loaded terminals.","salesMarkdown":"The integrated diode handles the coil's flyback voltage, so you can omit an external free-wheel diode on the panel wiring. The spring-loaded terminals accept 0.2–2.5 mm² solid or ferruled stranded wire; strip length is typically 8–10 mm. The DC 24 V coil draws about 0.2 A steady-state, so a standard 24 VDC power supply with a few hundred mA headroom per contactor is sufficient. The integrated diode means no separate snubber is needed across the coil terminals.","metaTitle":"Siemens 3RT2015-2FB41-ZX95 Contactor, AC-3, 3kW/400V, DC 24V","metaDescription":"Siemens 3RT2015-2FB41-ZX95 contactor, AC-3 rated 3kW/400V, 1NO, DC 24V coil with integrated diode. Size S00, spring-loaded terminals. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f66e91d3065f099066772c707ab57c2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=95487&mlfb=3RT2015-2FB41-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2015-2FB41-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT2015-2FB41-ZX95 and how is it quoted?","answer":"This part is sourced and quoted to order through independent distribution against an RFQ. Availability and current pricing are confirmed at the time of quote."},{"question":"What does the AC-3 3 kW/400 V rating mean for this contactor?","answer":"The AC-3 rating of 3 kW at 400 V means this contactor is designed for switching three-phase induction motors up to that power level during starting and running — the standard duty class for motor loads, not resistive heating."},{"question":"What is the coil voltage and does it have built-in suppression?","answer":"The coil is DC 24 V and includes an integrated suppression diode, so no external flyback diode is needed across the coil terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2015-2FB41-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2015-2FB41-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}