{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2016-1AB02-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2016-1AB02-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT2016-1AB02-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2016-1AB02-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2016-1AB02-ZX95, size S00 power contactor, 24 VDC coil, screw-type terminals, snap-on DIN rail mount.","salesMarkdown":"The 24 VDC coil pulls in at 10 A at rated voltage — that's the inrush, not the hold. The auxiliary contacts are rated for switching at various DC voltages: 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. These are DC-13 type loads typically — solenoids, contactor coils, indicator lamps. If you're switching a 24 VDC PLC output to a pilot light, the 10 A rating gives plenty of headroom; at 125 VDC the 0.9 A limit means you can't parallel multiple heavy loads on one auxiliary contact. Switching frequency limits are stated per duty: 1 000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2 and AC-3 (motor starting/running), and 250 cycles/hour at AC-4 (plugging/inching). The AC-3e rating also caps at 750 cycles/hour. For a conveyor motor cycling every 5 seconds, that 750 cycles/hour limit means you can't exceed about one start every 4.8 seconds continuous — stay under it or the contactor overheats. That gives flexibility for tight enclosures, but keep the ambient within the operating range — the coil and contacts derate above 60 °C. The contactor measures 45 mm wide, 58 mm high, and 73 mm deep — size S00 footprint. It snaps onto a 35 mm DIN rail; clearance requirements: 10 mm upwards, 10 mm forwards, 10 mm downwards, and 6 mm at the side. That's tight — you can pack several contactors side by side on the rail, but leave the 6 mm side gap for airflow and wiring access. Main and auxiliary terminals accept solid or stranded wire: 0.5 to 4 mm² for single conductors, and up to 2x 4 mm² or 2x (0.75 to 2.5 mm²) for two conductors per clamp. Screw-type terminals.","metaTitle":"Siemens SIRIUS 3RT2016-1AB02-ZX95 Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT2016-1AB02-ZX95 power contactor, size S00, 24 VDC coil, screw terminals. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"7 ... 13 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"1 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"7.6 A","at 50 Hz rated value":"24 V","at 500 V rated value":"2 A","at 60 Hz rated value":"24 V","at 600 V rated value":"9 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"2.1 W","at AC-2 at 400 V rated value":"4 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"7.4 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.2 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.7 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"155 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"111 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"66 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"55 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/485d6ce3689089d697f892da20559e94.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=105853&mlfb=3RT2016-1AB02-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2016-1AB02-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"Width 45 mm, height 58 mm, depth 73 mm. Clearance: 10 mm upwards, 10 mm forwards, 10 mm downwards, 6 mm at the side."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2016-1AB02-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2016-1AB02-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}