{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2016-1AV62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2016-1AV62","canonicalUrl":"https://aoctrl.com/siemens/3RT2016-1AV62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2016-1AV62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 VDC coil, screw-type terminals, auxiliary switch, screw and snap-on DIN rail mount.","salesMarkdown":"Rated for AC-3 maximum switching frequency of 750 operating cycles per hour, and AC-4 at 250 cycles per hour — the AC-4 figure is the one that governs severe plugging or inching duty, so size the application against that, not the AC-3 headline. The 24 V rating is the full-load ampacity for a typical PLC-level signal; at 400 V the contact still carries 3 A for pilot-duty loads. The -25 °C low end is the floor for cold panel starts — no pre-heat required for a typical unheated enclosure in temperate climates. Terminals accept solid or stranded wire from 0.5 to 4 mm², and up to 2x 4 mm² or 2x (0.75...2.5 mm²) for paralleled feeds. The screw-type clamp is standard for panel-builds where ring or fork terminals are preferred over spring cages.","metaTitle":"Siemens 3RT2016-1AV62 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens 3RT2016-1AV62 SIRIUS power contactor, size S00, 24 VDC coil, screw terminals. Current production. Auxiliary switch included. Screw and snap-on DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"7 ... 13 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"1 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"7.6 A","at 500 V rated value":"2 A","at 60 Hz rated value":"480 V","at 600 V rated value":"9 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"0.9 W","at AC-2 at 400 V rated value":"4 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"7.4 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.8 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.3 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"155 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"111 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"66 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"55 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cd30cb46d8185bc03a432166a57d1a25.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=36590&mlfb=3RT2016-1AV62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2016-1AV62/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT2016-1AV62?","answer":"The 3RT2016-1AP01-ZX95 is a peer variant in the same S00 frame size. The key difference is the coil voltage — the 1AV62 uses 24 VDC, while the 1AP01 uses a different coil rating. Panel wiring and mounting footprint are identical."},{"question":"What compliance documentation is available for this contactor?","answer":"The SIRIUS series carries CE, UL, CSA, and IEC certifications per standard Siemens documentation. RoHS and REACH declarations are available through the manufacturer's document portal."},{"question":"Will 3RT2016-1AV62 fit a panel designed for 3RT2016-1AP01-ZX95?","answer":"Yes — same S00 frame size, same 45 mm width, same screw and snap-on DIN rail mount. The only difference is the coil voltage; wiring and mechanical fit are identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2016-1AV62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2016-1AV62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}