{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2016-2AB02-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2016-2AB02-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2016-2AB02-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2016-2AB02-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2016-2AB02-ZW96, size S00 power contactor, 24 VDC coil, spring-type terminals, screw and snap-on DIN rail mount.","salesMarkdown":"The 3RT2016-2AB02-ZW96: The coil is 24 VDC, terminated with spring-type terminals, and the main contacts are rated for AC-3 duty at 750 switching cycles per hour maximum. It mounts via screw or snap-on onto a 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface, plus +/-22.5° tilt forward/backward. Switching frequency varies by duty class: 1,000 cycles/hour for AC-1 (resistive), 750 cycles/hour for AC-2 and AC-3 (motor start/run), and 250 cycles/hour for AC-4 (plugging/inching). The AC-3e rating also caps at 750 cycles/hour. The auxiliary switch is rated for 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V — these are the make/break capacities for the auxiliary contacts, not the main poles. The SIRIUS S00 platform is widely used, and the 3RT2016 base model is a common BOM line item. The -ZW96 suffix indicates a special variant.","metaTitle":"Siemens 3RT2016-2AB02-ZW96 SIRIUS S00 Power Contactor, 24 VD","metaDescription":"Siemens SIRIUS 3RT2016-2AB02-ZW96 power contactor, size S00, 24 VDC coil, spring-type terminals, screw and snap-on DIN rail mount. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","title":"3RT2016-2AB02-ZW96","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"CONTACTOR, AC-3, 4KW/400V, 1NC, AC 24V, 50/60 HZ, 3-POLE, SZ S00 SPRING-LOADED TERMINAL MULTI UNIT PACKAGE PACKAGE = 60 UNITS","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"1 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"7.6 A","at 50 Hz rated value":"24 V","at 500 V rated value":"2 A","at 60 Hz rated value":"24 V","at 600 V rated value":"9 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"0.9 W","at AC-2 at 400 V rated value":"4 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 12)","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"7.4 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.2 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 12)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.3 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"155 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"111 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"66 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"55 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e2ae4d1de8d9fd7525ded98952c5e8d7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=345963&mlfb=3RT2016-2AB02-ZW96"},"ai":{"faq":[{"question":"What is the depth of this contactor?","answer":"The depth is 73 mm, with a height of 70 mm and width of 45 mm."},{"question":"What wire sizes does the spring terminal accept?","answer":"The spring-type terminals accept solid or stranded wire from 0.5 to 4 mm², and 2x (0.5 to 4 mm²) for paralleled conductors."},{"question":"What compliance documentation is available for this part?","answer":"As a Siemens SIRIUS product, it typically carries CE, UL, CSA, and CCC certifications, and is RoHS and REACH compliant. Specific documentation (declaration of conformity, UL file number) is available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2016-2AB02-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2016-2AB02-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}