{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2016-2JB41-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2016-2JB41-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2016-2JB41-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2016-2JB41-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS coupling contactor, 3RT2016-2JB41-ZW96, size S00, 24 VDC coil, spring-type terminals, 10 A at 24 VDC.","salesMarkdown":"The spring-type terminals accept solid or stranded wire from 0.5 to 4 mm², and up to 2x (0.5 to 4 mm²) per clamp, which covers most control-circuit wiring without needing ferrules or bootlace crimps. At 48 V and 60 V the rating drops to 2 A, and at 125 V to 0.9 A, reflecting the arc-quenching limits of a DC contactor. For AC motor loads this is not the right part; it is a coupling contactor, meaning it isolates control signals or switches DC auxiliaries, not main motor power. Coil draw is 24 VDC with a holding power factor of 0.7 initial, 1.25 full-scale — the magnet coil holds closed at rated voltage, drops out cleanly below the dropout threshold. Mechanical life is typical 30 million operations; electrical life at AC-3 is 750 cycles per hour maximum, and at AC-4 (frequent inching/plugging) it is 250 cycles per hour. ## Mounting and Clearance Notes The contactor is 70 mm high, 45 mm wide, 73 mm deep. The 3RT2016-2JB41-ZW96 is size S00; it will not drop into a panel wired for an S0 frame without changing the DIN rail footprint and rewiring the terminations. If your panel was spec'd around the 3RT2024-2BB40, the 3RT2016-2JB41-ZW96 is not a direct mechanical substitute.","metaTitle":"Siemens 3RT2016-2JB41-ZW96 SIRIUS Coupling Contactor, 24 VDC","metaDescription":"Siemens 3RT2016-2JB41-ZW96 SIRIUS coupling contactor, size S00, 24 VDC coil, 10 A at 24 VDC. Spring-type terminals. Current production. RFQ for pricing and lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at DC":"38 ... 65 ms","title":"3RT2016-2JB41-ZW96","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","Rated Value":"24 V","description":"COUPLING RELAY, AC-3, 4KW/400V, 1NO, DC 24V, 0.7...1.25*US, W. INTEGRATED DIODE 3-POLE SZ S00, SPRING-LOADED TERMINAL MULTI-UNIT PACKAGING 60 PIECES","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Full-Scale Value":"1.25","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Coupling contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"1 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"7.6 A","at 500 V rated value":"2 A","at 600 V rated value":"9 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"2.1 W","at AC-2 at 400 V rated value":"4 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Design Of The Surge Suppressor":"diode","at AWG cables for main contacts":"2x (20 ... 12)","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"7.4 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"2.8 W","closing power of magnet coil at DC":"2.8 W","holding power of magnet coil at DC":"2.8 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 12)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.7 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"No","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"155 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"111 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"66 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"55 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fe950458324d3f463c78263ff98f44a0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=396240&mlfb=3RT2016-2JB41-ZW96"},"ai":{"faq":[{"question":"What is the closest functional second-source to the 3RT2016-2JB41-ZW96?","answer":"The closest functional peer is the 3RT2024-2BB40, but it is a larger S0 frame size. The 3RT2016-2JB41-ZW96 is size S00, so a panel built for the S0 frame would need mechanical and wiring changes to accept this contactor."},{"question":"What wire sizes does the spring terminal accept?","answer":"Solid or stranded wire from 0.5 to 4 mm² per clamp, and up to 2x (0.5 to 4 mm²) per terminal."},{"question":"Will the 3RT2016-2JB41-ZW96 drop into a panel spec'd around the 3RT2024-2BB40?","answer":"No. The 3RT2016-2JB41-ZW96 is size S00 (45 mm wide), while the 3RT2024-2BB40 is size S0 (wider footprint). The DIN rail hole pattern and terminal layout differ; rewiring and a different mounting rail position would be required."},{"question":"What compliance documentation is available for this part?","answer":"As a current-production Siemens SIRIUS component, it carries CE marking and is designed to meet relevant IEC/EN standards for contactors. Specific RoHS/REACH declarations and UL/CSA certifications should be confirmed against the factory nameplate or the official Siemens declaration of conformity for the exact order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2016-2JB41-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2016-2JB41-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}