{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2016-4AP62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2016-4AP62","canonicalUrl":"https://aoctrl.com/siemens/3RT2016-4AP62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2016-4AP62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2016-4AP62 power contactor, Size S00, 45 mm width, 73 mm depth, 58 mm height, screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715.","salesMarkdown":"## Duty cycle and switching frequency The 3RT2016-4AP62: Maximum switching rates: 1,000 cycles/hour in AC-1 (resistive load), 750 cycles/hour in AC-3 (motor starting), and 250 cycles/hour in AC-4 (plugging/inching) — the AC-4 ceiling is the one that governs high-duty applications like reversing or jogging. Arcing time spans 10 to 15 ms at AC, which sets the minimum off-time between switching operations to avoid contact welding. ## Auxiliary contact ratings for control circuits The magnet coil connection uses ring cable lugs — plan the control wiring with ring terminals rather than fork or pin types. ## Thermal environment and storage Coil rated for 50 Hz at 220 V and 60 Hz at 240 V — the 0.24 A holding current at both frequencies means the control transformer sizing is the same regardless of line frequency.","metaTitle":"Siemens 3RT2016-4AP62 SIRIUS Contactor, Size S00, 45 mm","metaDescription":"Siemens 3RT2016-4AP62 SIRIUS power contactor, Size S00 frame, 45 mm width, screw and snap-on DIN rail mount. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"4 ... 15 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.24","at 60 Hz":"0.24","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Ring cable lug connection","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"1 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"7.6 A","at 50 Hz rated value":"220 V","at 500 V rated value":"2 A","at 60 Hz rated value":"240 V","at 600 V rated value":"9 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"Ring cable lug connection","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"7.5 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"0.9 W","at AC-2 at 400 V rated value":"4 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"7.4 A","For Auxiliary And Control Circuit":"ring terminal lug connection","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4.4 W","At Contactor For Auxiliary Contacts":"Ring cable lug connection","With Type Of Coordination 1 Required":"gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.3 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"155 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"111 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"86 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"66 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"55 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2797dceb19572e3a39af16abf25f8d8f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=73289&mlfb=3RT2016-4AP62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2016-4AP62/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2016-4AP62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2016-4AP62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}