{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-1AG61","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-1AG61","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-1AG61","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1AG61","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2017-1AG61 power contactor, Size S00, 24 VDC coil, screw-type terminals, screw and snap-on mounting onto 35 mm DIN rail (DIN EN 60715), depth 73 mm.","salesMarkdown":"The Siemens SIRIUS 3RT2017-1AG61 is a Size S00 power contactor with a 24 VDC magnet coil and screw-type terminals. It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, fitting a standard panel footprint at 45 mm wide and 73 mm deep. ## Ratings and operating conditions Rated for AC-1 resistive loads at 1000 operating cycles per hour, AC-3 motor switching at 750 ops/h, and AC-4 inching/plugging at 250 ops/h. The AC-3e rating matches the 750 ops/h figure. Mechanical life is typical 30 million operations. Ambient operating range -25 to +60 °C; storage range -55 to +80 °C. Mounting position allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward/backward on vertical. Clearances: 10 mm upward, 10 mm forward, 10 mm downward, 6 mm at the side. Accepts solid or stranded wire: 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm². Stranded alone 0.5...4 mm².","metaTitle":"Siemens SIRIUS 3RT2017-1AG61 Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT2017-1AG61 power contactor, Size S00, 24 VDC coil, screw terminals, screw and snap-on DIN rail mounting. Rated AC-1 1000 ops/h, AC-3 750 ops/h. Current production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","title":"3RT2017-1AG61","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.24","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 100 V AC, 50 Hz / 100-110 V, 60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"100 V","at 500 V rated value":"2 A","at 60 Hz rated value":"110 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"6.5 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$22.86","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e237e3a74ab1e1d41e1094b03697f6c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=525916&mlfb=3RT2017-1AG61"},"ai":{"faq":[{"question":"Where can I buy 3RT2017-1AG61 and how do I get a price?","answer":"The 3RT2017-1AG61 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is 3RT2017-1AG61's listed depth (73 mm) on this component line?","answer":"The listed depth is 73 mm."},{"question":"What is 3RT2017-1AG61's listed solid (0.5... 4 mm²) on this component line?","answer":"The solid wire range is 0.5... 4 mm²."},{"question":"Will 3RT2017-1AG61 drop into a panel that was specified around 3RT2016-1AH01 without rewiring?","answer":"Both are Size S00 contactors with screw terminals and the same DIN rail mounting, so the 3RT2017-1AG61 will physically fit the same footprint. However, the coil voltage differs (24 VDC vs the 3RT2016-1AH01's 110 VAC 50/60 Hz), so the control circuit must match the new coil voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-1AG61","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-1AG61 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}