{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-1AK64-3MA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-1AK64-3MA0","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-1AK64-3MA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1AK64-3MA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2017-1AK64-3MA0 power contactor, size S00, 45 mm width, screw and snap-on mounting onto 35 mm DIN rail, screw-type coil terminals, no auxiliary switch.","salesMarkdown":"## SIRIUS S00 contactor — panel fit and duty-cycle limits The 3RT2017-1AK64-3MA0 is a SIRIUS power contactor in size S00, 45 mm wide, 58 mm tall, 117 mm deep — the compact footprint fits standard 35 mm DIN rail per DIN EN 60715, with screw and snap-on fastening. Rated for 750 operating cycles per hour in AC-3 and AC-3e duty, and 250 ops/h in AC-4 — the switching frequency limit drops by a factor of three under the higher electrical stress of plugging/inching service. Mechanical endurance is 30 million cycles typical, so the contactor outlasts the panel's service life in most conveyor, pump, and fan applications at the rated switching rates. Operating temperature range is -25 to +60 °C, storage -55 to +80 °C — the wider storage envelope covers unpowered shelf life in unconditioned warehouses. ## Termination and wiring — screw-type coil terminals, no auxiliary Main contact terminals accept solid or stranded wire from 0.5 to 4 mm², with dual-wire capacity: 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm² — enough for paralleled feeds or daisy-chaining in a motor starter cluster. The magnet coil uses screw-type terminals, and the contactor ships without an auxiliary switch block — if you need a mirror contact or early-make signal, a separate SIRIUS auxiliary switch must be added to the front or side slot. Clearance distances: 10 mm upwards, 10 mm forwards, 10 mm downwards, 6 mm at the side — these are the minimum air gaps to adjacent metalwork or enclosure walls for the rated insulation voltage. ## Mounting position flexibility The contactor can be mounted in any orientation: +/-180° rotation on a vertical surface, and tilted forward or backward by +/-22.5° on a vertical surface — useful when the panel layout forces a non-standard angle. ## Coil operating current across voltages The coil draws 6 A at 24 V rated value, dropping to 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 0.2 A at 440 V — these are the steady-state holding currents; inrush at pickup is higher but the PLC output or relay driving the coil must be rated for the holding current plus a margin for the initial surge. ## Lifecycle and sourcing — active production, quoted to order Sourced through independent distribution channels; availability and current pricing are confirmed at RFQ against the BOM quantity. No stock-holding claim — quoted per order.","metaTitle":"Siemens 3RT2017-1AK64-3MA0 SIRIUS Power Contactor, Size S00","metaDescription":"Siemens 3RT2017-1AK64-3MA0 SIRIUS power contactor, size S00, 45 mm width, screw and snap-on DIN rail mount. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"117 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","title":"3RT2017-1AK64-3MA0","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.24","at 60 Hz":"0.24","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 110 V AC, 50 Hz / 120 V, 60 Hz, auxiliary contacts: 2 NO + 2 NC, screw terminal, size: S00, captive auxiliary switch","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"110 V","at 500 V rated value":"2 A","at 60 Hz rated value":"120 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-2 at 400 V rated value":"5.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"5.9 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$26.67","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6f9c1b882f369482d3a315d9988770c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=80197&mlfb=3RT2017-1AK64-3MA0"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RT2017-1AK64-3MA0?","answer":"The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC) for this order code. Standard SIRIUS contactors typically carry CE, UL, and CSA marks — verify the nameplate or request the declaration from the supplier at RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-1AK64-3MA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-1AK64-3MA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}