{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-1AP01-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-1AP01-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-1AP01-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1AP01-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS Size S00 power contactor, 3RT2017-1AP01-ZW96, 24 VDC coil, screw-type terminals, 45 mm width, current-production lifecycle stage.","salesMarkdown":"The auxiliary switch block is integrated, saving a slot on the rail. ## Auxiliary contact ratings and switching frequency The auxiliary contacts carry 10 A at 24 V, 2 A at 48 V or 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V. These are the rated values for the integrated auxiliary switch — check your control circuit voltage against these curves. Switching frequency limits: 1 000 operations/hour at AC-1, 750/h at AC-2, AC-3, and AC-3e, and 250/h at AC-4. For high-cycle applications like rapid reversing, stay within the AC-4 ceiling. ## Wiring and clearances Terminals accept solid or stranded wire from 0.5 to 4 mm², with dual-wire capacity: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². Minimum clearances to adjacent components: 10 mm upward, forward, and downward; 6 mm at the sides. This order code is at a current-production lifecycle stage. No official successor has been issued.","metaTitle":"Siemens 3RT2017-1AP01-ZW96 SIRIUS Power Contactor, Size S00","metaDescription":"Siemens SIRIUS 3RT2017-1AP01-ZW96 Size S00 power contactor, 24 VDC coil, screw terminals, 45 mm wide. Current-production lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"230 V","at 500 V rated value":"2 A","at 60 Hz rated value":"230 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-2 at 400 V rated value":"5.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"5.7 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bb8e66f5015b78fcac871b3d66f465e4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=244026&mlfb=3RT2017-1AP01-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1AP01-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT2017-1AP01-ZW96 and get a price?","answer":"This part is sourced through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time, not listed here."},{"question":"What are the key ratings of 3RT2017-1AP01-ZW96?","answer":"It is a Size S00 power contactor with a 24 VDC screw-type coil, 45 mm wide, auxiliary contacts rated from 10 A at 24 V down to 0.2 A at 440 V, and switching frequencies up to 1 000 ops/h at AC-1."},{"question":"What compliance documentation is available for 3RT2017-1AP01-ZW96?","answer":"As a Siemens SIRIUS product, standard compliance documentation (CE, UL, CSA, RoHS, REACH) is typically available from the manufacturer. Specific certs for this order code should be verified against the product marking or requested at quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-1AP01-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-1AP01-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}