{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-1VB41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-1VB41","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-1VB41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1VB41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS coupling contactor, size S00, 3RT2017-1VB41, 24 VDC coil, screw-type terminals, 10 A at 24 VDC, 45 x 58 x 73 mm.","salesMarkdown":"Siemens SIRIUS 3RT2017-1VB41 is a coupling contactor in size S00. Coil rated at 24 VDC with pickup at 0.85 × rated and dropout at 1.85 × rated. Main contacts switch 10 A at 24 VDC, derating to 2 A at 48–60 VDC and 1 A at 110 VDC. For a 230 VAC motor load the contactor is rated 2 hp. Mechanical service life is 30 million operations typical, with maximum operating frequencies of 1000 cycles/hour at AC-1 (resistive), 750/h at AC-2 and AC-3 (motor start/run), and 250/h at AC-4 (plugging/inching). For high-cycle applications like pick-and-place or valve banks, stay under the AC-1 limit and the 750/h ceiling for motor duty. Wire range accepts 0.5–4 mm² solid or stranded, with two conductors per terminal up to 2×2.5 mm². Screw-type terminals on the coil and main contacts — no push-in or spring-cage, so factor in screwdriver torque time during panel build. Clearance to adjacent components: 10 mm upward, downward, and forward; 6 mm to the side. That 6 mm side gap is tighter than typical — adjacent contactors need that minimum to avoid magnetic interaction or heat buildup. No special derating needed for most control cabinet environments, but if the panel sits near a heat source or in direct sunlight, keep internal cabinet temp under 60 °C.","metaTitle":"Siemens SIRIUS 3RT2017-1VB41 Coupling Contactor, Size S00, 2","metaDescription":"Siemens SIRIUS 3RT2017-1VB41 coupling contactor, size S00, 24 VDC coil, screw terminals, 10 A at 24 VDC. Active production. DIN rail mount. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at DC":"20 ... 80 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","Rated Value":"24 V","Initial Value":"0.85","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Full-Scale Value":"1.85","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Coupling contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 500 V rated value":"2 A","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Design Of The Surge Suppressor":"diode","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"1.6 W","closing power of magnet coil at DC":"1.6 W","holding power of magnet coil at DC":"1.6 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 2x 12","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"No","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/092a39bf510b666f994ae22473c67227.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=144326&mlfb=3RT2017-1VB41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2017-1VB41/alternatives.json"},"ai":{"faq":[{"question":"What wire sizes does this contactor accept?","answer":"Solid or stranded 0.5–4 mm². For two conductors: 2×(0.5–1.5 mm²), 2×(0.75–2.5 mm²), or 2×4 mm². Screw-type terminals."},{"question":"What compliance documentation does Siemens provide for this contactor?","answer":"Standard SIRIUS contactors carry CE marking for the European market and UL/CSA listings for North America. RoHS and REACH declarations are available through Siemens Industry Online Support. The product is designed to IEC 60947-4-1 for contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-1VB41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-1VB41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}