{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-2AB01-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-2AB01-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-2AB01-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-2AB01-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT2017-2AB01-ZW96, size S00, 45 mm width, spring-type coil terminals, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"Its 45 mm width and 73 mm depth fit standard DIN-rail enclosures with screw and snap-on mounting per DIN EN 60715. The contactor carries an auxiliary switch and spring-type terminals on the coil, accepting solid or stranded conductors from 0.5 to 4 mm². Mechanical service life is rated at 30,000,000 operations typical. ## Switching Performance and Duty Ratings Maximum switching frequency varies by duty class: 1,000 cycles/hour at AC-1 (resistive), 750 cycles/hour at AC-2 and AC-3 (motor start/run), and 250 cycles/hour at AC-4 (plugging/inching). The AC-3e rating also caps at 750 cycles/hour, matching standard motor switching. Arcing time spans 10 to 15 ms at AC, and the main contacts are rated for 20 to 12 — the range covering typical motor inrush and running currents for this frame size. ## Mounting and Clearance Requirements Mounting position allows ±180° rotation on a vertical surface and ±22.5° tilt forward/backward. Required clearances: 10 mm upward, 10 mm downward, 10 mm forward, 6 mm at the side — critical for heat dissipation and arc flash containment in tight panels. Operating temperature range is -25 to +60 °C during operation, with storage from -55 to +80 °C.","metaTitle":"Siemens SIRIUS 3RT2017-2AB01-ZW96 Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS power contactor 3RT2017-2AB01-ZW96, size S00, 45mm wide. AC-3 switching at 750 cycles/h. Screw and snap-on DIN rail mount. Current lifecycle stage. RFQ for sourcing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","title":"3RT2017-2AB01-ZW96","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"CONTACTOR, AC-3, 5.5KW/400V, 1NO, AC 24V, 50/60 HZ, 3-POLE, SZ S00, SPRING-LOADED TERMINAL MULTI UNIT PACKAGE PACKAGE = 60 UNITS","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"24 V","at 500 V rated value":"2 A","at 60 Hz rated value":"24 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-2 at 400 V rated value":"5.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","at AWG cables for main contacts":"2x (20 ... 12)","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"5.7 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 12)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/77b084f6f9e4f1e6edfa4b34badd9490.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=65445&mlfb=3RT2017-2AB01-ZW96"},"ai":{"faq":[{"question":"What are the key dimensions and clearances for panel integration?","answer":"The contactor measures 45 mm wide, 70 mm high, and 73 mm deep. Required clearances are 10 mm upward, downward, and forward, with 6 mm at the sides for proper ventilation and arc containment."},{"question":"What conductor sizes does the spring-type coil terminal accept?","answer":"The spring-type terminals accept solid or stranded conductors from 0.5 to 4 mm², including 2x (0.5 to 4 mm²) for parallel runs."},{"question":"What switching frequencies can this contactor handle?","answer":"Maximum switching frequency depends on duty: 1,000 cycles/hour at AC-1, 750 cycles/hour at AC-2, AC-3, and AC-3e, and 250 cycles/hour at AC-4 for heavy inching/plugging duty."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-2AB01-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-2AB01-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}