{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-2AN22","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-2AN22","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-2AN22","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-2AN22","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT2017-2AN22, Size S00, spring-type terminals for coil, 24 VDC coil, auxiliary switch included, screw and snap-on DIN rail mount.","salesMarkdown":"## Core identity and fit It uses spring-type terminals for the magnet coil connection, accepting solid or stranded conductors from 0.5 to 4 mm², and mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. The auxiliary contact block on this contactor is rated for 10 A at 24 V, dropping to 0.2 A at 440 V — that's the switching capacity across the voltage range, not the continuous carry current. For motor duty, the contactor is specified for 750 operations per hour at AC-3 and AC-3e, and 250 at AC-4, which governs jogging or reversing applications. The main contacts have a mechanical life of 30 million operations, meaning the coil and armature outlast the arc erosion on the contacts in a well-sized application. ## Thermal and mounting constraints ## Switching performance and losses Maximum switching frequency varies by duty: 1000 ops/h at AC-1 (resistive), 750 at AC-2 and AC-3, and 250 at AC-4.","metaTitle":"Siemens SIRIUS 3RT2017-2AN22 Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT2017-2AN22 power contactor, Size S00, spring-type coil terminals, 24 VDC rated 10 A auxiliary. Active lifecycle. DIN rail mount. Operates -25 to +60 °C.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"220 V","at 500 V rated value":"2 A","at 60 Hz rated value":"220 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-2 at 400 V rated value":"5.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"5.7 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 12)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=44591&mlfb=3RT2017-2AN22","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2017-2AN22/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative?","answer":"The 3RT2017-2AP01-ZW96 is a variant with the same Size S00 frame and contactor core, but differs in coil termination and auxiliary configuration. Verify the coil voltage and terminal type before substituting — the 2AN22 uses spring-type coil terminals and includes an auxiliary switch."},{"question":"What are the key dimensions for panel layout?","answer":"Width is 45 mm, height is 70 mm, depth is 73 mm. It mounts on 35 mm DIN rail per DIN EN 60715, with 10 mm clearance needed upward, downward, and forward, and 6 mm at the sides."},{"question":"What conductor sizes does the spring-type terminal accept?","answer":"Solid or stranded conductors from 0.5 to 4 mm², and up to 2x (0.5 to 4 mm²) for fine-stranded wire."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-2AN22","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-2AN22 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}