{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-2JB42-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-2JB42-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-2JB42-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-2JB42-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS coupling contactor, Size S00, 3RT2017-2JB42-ZW96, 24 VDC coil, 10 A DC-13 rated, spring-type terminals, screw and snap-on 35 mm DIN rail.","salesMarkdown":"The 24 VDC coil pulls in at its rated value and the main contacts are rated for 10 A at 24 V DC-13 (switching electromagnets), with a DC-13 breaking capacity that drops as voltage rises — 2 A at 48 V and 60 V, 1 A at 110 V, 0.3 A at 220 V, and 3 A at 400 V. Spring-type terminals (cage clamp style) accept 0.5 to 4 mm² solid or stranded wire, and you can double up two conductors of the same cross-section per clamp. The Size S00 footprint is 45 mm wide, 70 mm tall, 73 mm deep — tight enough for crowded subpanels. Mounting position is flexible: you can rotate the contactor ±180° on a vertical surface or tilt it ±22.5° forward/backward. Clearance requirements are modest — 10 mm upward, downward, and forward, 6 mm to the side. The arcing time is 10 to 15 ms, and dropout time at DC is 38 to 65 ms, which matters when sequencing contactors in a safety circuit. The DC-13 rating is the one that governs real use: 10 A at 24 V means it can switch the inductive load of a medium-sized DC solenoid or brake, but if you're switching a resistive DC heater, the AC-1 rating (not explicitly listed here but implied by the contactor class) would be higher. The operating temperature range is -25 to +60 °C, storage -55 to +80 °C — fine for most indoor panels but watch the upper end near ovens or sunny enclosures. Mechanical life is typical 30 million operations; electrical life depends on the load and switching frequency — at AC-3 (motor) duty it's rated for 750 cycles per hour maximum, at AC-4 (inching/plugging) it drops to 250 cycles per hour. The auxiliary switch is not built in (listed as 'No'), so if you need a mirror contact or status feedback, you'll need to add a separate auxiliary contact block.","metaTitle":"Siemens 3RT2017-2JB42-ZW96 SIRIUS Coupling Contactor, Size S","metaDescription":"Siemens SIRIUS 3RT2017-2JB42-ZW96 coupling contactor, Size S00, 24 VDC coil, 10 A DC-13 rating, spring-type terminals. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at DC":"38 ... 65 ms","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","Rated Value":"24 V","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Full-Scale Value":"1.25","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Coupling contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 500 V rated value":"2 A","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","Safety-Related Switching On":"Yes","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-2 at 400 V rated value":"5.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Design Of The Surge Suppressor":"diode","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"2.8 W","closing power of magnet coil at DC":"2.8 W","holding power of magnet coil at DC":"2.8 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","for AWG cables for auxiliary contacts":"2x (20 ... 12)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f4d0dabf6ece39d25f0d4a0eb8b0c2eb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=309643&mlfb=3RT2017-2JB42-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2017-2JB42-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Will 3RT2017-2JB42-ZW96 drop into a panel specified around 3RT2016-1AG62 without rewiring?","answer":"Both are Size S00 with the same 45 mm width and DIN rail mounting, so the footprint and terminal layout are identical. The main difference is the coil voltage and current rating — verify your control voltage and load current before swapping, but mechanically it fits without panel modification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-2JB42-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-2JB42-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}