{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-4AG62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-4AG62","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-4AG62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-4AG62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2017-4AG62 power contactor, size S00, 45 mm width, 73 mm depth, 58 mm height, 100 V AC 50 Hz / 110 V AC 60 Hz coil, ring cable lug connection, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"## Panel fit and what the S00 frame means The 3RT2017-4AG62 is a SIRIUS size S00 contactor — the smallest frame in the Siemens SIRIUS family, measuring 45 mm wide, 73 mm deep, and 58 mm tall. That 45 mm width is the critical dimension for rail fill in a crowded panel; it fits two units per 90 mm section of DIN rail. Clearance distances are tight: 10 mm upwards, downwards, and forwards; 6 mm at the sides. ## Coil voltage and switching frequency limits Connection is via ring cable lug, not a push-on terminal, so factor in the lug crimping step during assembly. Switching frequency depends on the duty class: 1,000 operations per hour in AC-1 (resistive loads), 750 ops/h in AC-3 (motor starting) and AC-3e, but only 250 ops/h in AC-4 (plugging/reversing/inching). If your application involves frequent jogging or reversing, that 250 ops/h ceiling is the binding constraint — not the AC-3 number. Mechanical life is rated 30 million operations typical — that's the contactor frame and mechanism, not the contacts. Contact wear depends on your actual switching current and load type; the mechanical figure just tells you the actuator won't fatigue before the contacts need inspection. ## Auxiliary contact ratings at a glance This contactor includes an auxiliary switch. That 11 A at 480 V stands out — it's the highest current rating on the list, so if you're switching a 480 V control circuit, this auxiliary can handle it. ## Temperature range and storage The wider storage range matters if this contactor sits in a cold warehouse or a non-climate-controlled shipping container before installation.","metaTitle":"Siemens 3RT2017-4AG62 SIRIUS S00 Contactor, 100-110V Coil","metaDescription":"Siemens 3RT2017-4AG62 SIRIUS power contactor, size S00, 45mm wide, 100V/50Hz or 110V/60Hz coil. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at AC":"4 ... 15 ms","title":"3RT2017-4AG62","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","at 50 Hz":"0.24","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","description":"power contactor, AC-3e/AC-3, 12 A, 5.5 kW / 400 V, 3-pole, 100 V AC, 50 Hz / 100-110 V, 60 Hz, auxiliary contacts: 1 NC, ring cable lug connection, size: S00","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Ring cable lug connection","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 50 Hz rated value":"100 V","at 500 V rated value":"2 A","at 60 Hz rated value":"110 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"Ring cable lug connection","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"ring terminal lug connection","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"6.5 W","At Contactor For Auxiliary Contacts":"Ring cable lug connection","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a075a8959f23f5d0fa43f7a4f4a2ca53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=347817&mlfb=3RT2017-4AG62"},"ai":{"faq":[{"question":"What clearance distances are needed around the 3RT2017-4AG62?","answer":"Minimum clearances are 10 mm upwards, downwards, and forwards; 6 mm at the sides. The 6 mm side gap is the tightest — adjacent devices need that space for arc flash and heat dissipation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-4AG62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-4AG62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}