{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2017-4BB41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2017-4BB41","canonicalUrl":"https://aoctrl.com/siemens/3RT2017-4BB41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2017-4BB41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2017-4BB41, Size S00 power contactor, 24 VDC coil, ring cable lug connection, 45 x 58 x 73 mm, screw and snap-on 35 mm DIN rail.","salesMarkdown":"Its 24 VDC coil with a ring cable lug connection is a common control voltage for PLC-driven systems, and the contactor carries a 24 V rated operational current of 10 A, which governs its use for DC load switching at that voltage level. The contactor mounts via screw or snap-on onto a 35 mm DIN rail per DIN EN 60715, and the mounting position allows +/-180° rotation on a vertical surface plus +/-22.5° tilt forward and backward, giving panel builders flexibility in tight enclosures. The 10 A rating at 24 V is the headline DC-1 switching current for this contactor — it tells you the maximum resistive load current it can make and break at that voltage. For inductive DC loads (DC-3, DC-5), the ratings drop significantly: 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 230 V. These are the numbers that matter when you are switching solenoids, brakes, or DC motor fields — the 10 A figure is not a blanket rating. For AC motor duty (AC-3), the contactor is rated for 750 operating cycles per hour maximum, and for AC-1 resistive loads it can handle up to 1,000 cycles per hour. The coil connection uses a ring cable lug, so verify your wiring terminations match that format before panel assembly.","metaTitle":"Siemens SIRIUS 3RT2017-4BB41 Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT2017-4BB41 power contactor, Size S00, 24 VDC coil, 10 A at 24 V. Active production. Screw and snap-on DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Width":"45 mm","at DC":"7 ... 13 ms","Height":"58 mm","Upwards":"10 mm","Forwards":"10 mm","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","Rated Value":"24 V","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Ring cable lug connection","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Full-Scale Value":"1.1","at AC-3e maximum":"750 1/h","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"11 A","at 500 V rated value":"2 A","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Main Current Circuit":"Ring cable lug connection","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"7.5 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.5 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"8.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"9.9 A","For Auxiliary And Control Circuit":"ring terminal lug connection","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)","Without Load Current Share Typical":"4 W","closing power of magnet coil at DC":"4 W","holding power of magnet coil at DC":"4 W","At Contactor For Auxiliary Contacts":"Ring cable lug connection","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.5 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"200 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"123 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"61 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4d45db2cc2a00df44efd3cbcaf78b1b3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=318719&mlfb=3RT2017-4BB41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2017-4BB41/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"The contactor is 45 mm wide, 58 mm high, and 73 mm deep. Clearance requirements are 10 mm upwards, forwards, and downwards, plus 6 mm at the side."},{"question":"What is the 24 VDC switching capacity?","answer":"At 24 V rated value, the contactor is rated for 10 A. For higher DC voltages the rating drops per the DC-1 curve: 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 230 V."},{"question":"Does this contactor include an auxiliary contact?","answer":"Yes, it comes with an auxiliary switch built in, which can be used for status feedback or coil sealing."},{"question":"What mounting options does this contactor support?","answer":"It mounts via screw or snap-on onto a 35 mm DIN rail per DIN EN 60715. The mounting position allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward and backward."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2017-4BB41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2017-4BB41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}