{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2018-2AV01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2018-2AV01","canonicalUrl":"https://aoctrl.com/siemens/3RT2018-2AV01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2018-2AV01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2018-2AV01 power contactor, size S00, spring-type coil terminals, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"## Integrator's Spec Brief The coil connection uses spring-type terminals, while the main contacts accept solid or stranded conductors from 0.5 to 4 mm², or 2x (0.5 to 4 mm²) for paralleled feeds. For motor switching duty (AC-3), the maximum mechanical switching rate is 750 operations per hour, which governs how fast you can cycle a motor start/stop without overheating the contacts. The AC-4 (plugging/reversing) rate drops to 250 operations per hour, reflecting the higher electrical stress of inching or reversing under load. The typical mechanical service life is 30,000,000 operations. An auxiliary switch is included for status feedback. Spring-type coil terminals reduce wiring time compared to screw terminals — no torque driver needed for the coil circuit. Main contact torque range is 20 to 12 Nm (likely a range for different conductor sizes, though the evidence lists it as a range).","metaTitle":"Siemens 3RT2018-2AV01 SIRIUS Power Contactor, Size S00, 10A","metaDescription":"Siemens 3RT2018-2AV01 SIRIUS power contactor, size S00. Rated 10 A at 24 V. Spring-type coil terminals. Screw and snap-on 35 mm DIN rail mount. Current lifecycle stage. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"0.5 ... 4 mm²","Width":"45 mm","at AC":"4 ... 15 ms","Height":"70 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"0.5 ... 4 mm²","at 50 Hz":"0.25","at 60 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 15 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"20 ... 12","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"2 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.2 A","at 480 V rated value":"14 A","at 50 Hz rated value":"400 V","at 500 V rated value":"2 A","at 60 Hz rated value":"400 V","at 600 V rated value":"11 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 12","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","at 575/600 V rated value":"10 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"3 W","at AC-2 at 400 V rated value":"7.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"11.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"19.4 A","at AC-5b up to 400 V rated value":"13.2 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA)","Without Load Current Share Typical":"5.7 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 50A (690V,100kA), aM: 25A (690V,100kA), BS88: 50A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"1 W","for AWG cables for auxiliary contacts":"2x (20 ... 12)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes; with 3RH29","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"300 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"169 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"128 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"92 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"74 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"4 mm²","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=97611&mlfb=3RT2018-2AV01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2018-2AV01/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions and mounting requirements?","answer":"Width is 45 mm, height 70 mm, depth 73 mm. It mounts on 35 mm DIN rail per DIN EN 60715 via screw or snap-on. Required clearances: 10 mm up/down/forward, 6 mm to the side."},{"question":"What conductor sizes does the contactor accept?","answer":"Solid or stranded conductors from 0.5 to 4 mm². It also accepts 2x (0.5 to 4 mm²) for paralleled conductors. The coil connection uses spring-type terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2018-2AV01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2018-2AV01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}