{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2025-2BM40-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2025-2BM40-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT2025-2BM40-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2025-2BM40-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, S0 frame, spring-type terminals, 45 mm width, 107 mm depth, 102 mm height, rated for AC-3 switching at 1,000 operations per hour.","salesMarkdown":"## Switching Duty and Contact Ratings The contactor is rated for 1,000 operations per hour under AC-1, AC-2, AC-3, and AC-3e duty, and 300 ops/h under AC-4. AC-3 is the standard motor-switching category; AC-4 covers inching and plugging where the contacts make and break stalled-rotor current. The 1,000 ops/h ceiling means this contactor is sized for normal process cycling, not high-speed indexing. Auxiliary contact ratings are given at several DC voltage levels: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. These are the DC-13 switching limits for the auxiliary contacts — important when driving DC relays or PLC inputs from the same block. ## Environmental and Timing Specifications The storage limit governs handling during transport and off-season storage, not running conditions. Arcing time is 10 to 10 ms, and DC dropout time is 15 to 17.5 ms — these matter for coordination with upstream short-circuit protection and for timing interlock circuits. Wire range for main and auxiliary circuits: solid or stranded 1 to 10 mm², with a dual-wire capacity of 2x (0.5 to 2.5 mm²). The spring terminals accept ferruled stranded wire; strip length should follow the manufacturer's recommendation for spring-clamp terminations.","metaTitle":"Siemens 3RT2025-2BM40-ZX95 SIRIUS Power Contactor, S0 Frame,","metaDescription":"Siemens SIRIUS 3RT2025-2BM40-ZX95 power contactor, S0 frame, spring-type terminals, 45 mm wide. Rated for AC-3 switching at 1,000 ops/h. Current production. Quoted to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"107 mm","Width":"45 mm","Height":"102 mm","Arcing Time":"10 ... 10 ms","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/087ae4d6d3b0bead51521762c4901bdd.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=727382&mlfb=3RT2025-2BM40-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2025-2BM40-ZX95/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2025-2BM40-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2025-2BM40-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}