{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2025-2KC80","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2025-2KC80","canonicalUrl":"https://aoctrl.com/siemens/3RT2025-2KC80","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2025-2KC80","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S0 coupling contactor, 3RT2025-2KC80, 24 VDC coil, spring-type terminals, 10 A DC-13 at 24 V, 45 mm width, screw and snap-on 35 mm DIN rail.","salesMarkdown":"It's sized for control circuits that need to switch DC loads up to 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. The S0 frame keeps the footprint tight at 45 mm wide, 102 mm tall, and 107 mm deep — a standard slot on a 35 mm DIN rail per DIN EN 60715. Solid conductors from 1 to 10 mm², stranded from 1 to 10 mm², and 2x (0.5 to 2.5 mm²) for solid or stranded. ## Switching frequency by duty class Maximum switching frequency varies by duty: 1,000 1/h for AC-1, AC-2, AC-3, and AC-3e; drops to 300 1/h for AC-4. The AC-4 limit is the one that bites on reversing or inching applications — if your cycle rate pushes past 300 per hour, this contactor will overheat. Mechanical life is typical 10,000,000 operations. ## Environmental limits The storage limit is for handling and shelf life, not running — don't let a panel sit in a freezing warehouse and expect the contactor to pull in at -30 °C without pre-heating the coil.","metaTitle":"Siemens 3RT2025-2KC80 SIRIUS S0 Coupling Contactor, 24 VDC","metaDescription":"Siemens 3RT2025-2KC80 SIRIUS S0 coupling contactor. 24 VDC coil, spring-type terminals, 10 A at 24 V DC. Current lifecycle stage. Quoted to order. Sourced via independent distribut","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"107 mm","Solid":"1 ... 10 mm²","Width":"45 mm","at DC":"19 ... 21 ms","Height":"102 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","Downwards":"10 mm","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","Rated Value":"34 V","Initial Value":"0.7","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"1 000 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Full-Scale Value":"1.25","at AC-3e maximum":"1 000 1/h","For Main Contacts":"18 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Coupling contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"3 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"14 A","at 500 V rated value":"2 A","at 600 V rated value":"17 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","at 575/600 V rated value":"15 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"1.8 W","at AC-2 at 400 V rated value":"7.5 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"15.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Design Of The Surge Suppressor":"with varistor","at AWG cables for main contacts":"2x (18 ... 8)","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"35.2 A","at AC-5b up to 400 V rated value":"14.1 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 25A (690V,100kA), aM: 20A (690V,100kA), BS88: 25A (415V,80kA)","Without Load Current Share Typical":"4.5 W","closing power of magnet coil at DC":"4.5 W","holding power of magnet coil at DC":"4.5 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 63A (690V,100kA), aM: 32A (690V,100kA), BS88: 63A (415V,80kA)","at AWG cables for auxiliary contacts":"2x (20 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"0.6 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"DC","Limited To 1 S Switching At Zero Current Maximum":"225 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"225 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"180 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"115 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"96 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ceea13b7de3a9d6a0322d464dc5f1da7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=26491&mlfb=3RT2025-2KC80","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2025-2KC80/alternatives.json"},"ai":{"faq":[{"question":"What are the key DC switching ratings for 3RT2025-2KC80?","answer":"At 24 V DC rated value it switches 10 A; at 48 V DC, 2 A; at 60 V DC, 2 A; at 110 V DC, 1 A; at 125 V DC, 0.9 A; at 220 V DC, 0.3 A; at 400 V DC, 3 A."},{"question":"What conductor sizes does the 3RT2025-2KC80 accept?","answer":"Solid conductors from 1 to 10 mm²; stranded from 1 to 10 mm²; and 2x (0.5 to 2.5 mm²) for solid or stranded."},{"question":"How do I get current pricing and availability for 3RT2025-2KC80?","answer":"Submit an RFQ through this listing. The part is sourced and quoted to order via independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3RT2025-2KC80?","answer":"The depth is 107 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2025-2KC80","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2025-2KC80 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}