{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2026-1AP60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2026-1AP60","canonicalUrl":"https://aoctrl.com/siemens/3RT2026-1AP60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2026-1AP60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2026-1AP60 power contactor, AC-3e/AC-3, 25 A, 11 kW / 400 V, 3-pole, 220 V AC coil 50 Hz / 240 V 60 Hz, 1 NO + 1 NC auxiliary, screw terminals, size S0, DIN rail mount.","salesMarkdown":"## What this SIRIUS contactor is rated for The 3RT2026-1AP60: That AC-3 rating means it's built for starting and stopping squirrel-cage motors — the contacts handle the inrush without welding, and the 750 cycles-per-hour maximum at AC-3 keeps the thermal rise within the coil's duty cycle. The coil pulls 0.25 A at 50 Hz and 0.28 A at 60 Hz, so the control transformer sizing is straightforward. That covers most PLC feedback and interlocking needs without adding a side-mount block. ## Panel fit and wiring constraints That depth includes the coil terminals; when you're laying out a row of contactors, the 97 mm projection from the rail is the dimension to watch for enclosure depth. Torque range for the main contacts is 16 to 8 N·m — that's a wide band, so set the driver to the upper end for 10 mm² and back off for the smaller gauges.","metaTitle":"Siemens 3RT2026-1AP60 SIRIUS Contactor, 25 A, 11 kW / 400 V","metaDescription":"Siemens 3RT2026-1AP60 SIRIUS power contactor, AC-3e/AC-3 rated 25 A, 11 kW at 400 V, 3-pole, 220 V AC coil, 1 NO + 1 NC auxiliary, screw terminals, size S0.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"1 ... 10 mm²","Width":"45 mm","at AC":"4 ... 16 ms","Height":"85 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","at 60 Hz":"0.28","Downwards":"10 mm","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"16 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"3 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"21 A","at 50 Hz rated value":"220 V","at 500 V rated value":"2 A","at 60 Hz rated value":"240 V","at 600 V rated value":"22 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"5 hp","at 220/230 V rated value":"7.5 hp","at 460/480 V rated value":"15 hp","at 575/600 V rated value":"20 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"5.7 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"15.5 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"35.2 A","at AC-5b up to 400 V rated value":"20.7 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V, 80kA)","Without Load Current Share Typical":"10.5 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 kA)","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"1.9 W","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"375 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"300 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"210 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"144 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"118 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$38.10","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8754c779bf51a6bbb564291e3efc86d5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=21753&mlfb=3RT2026-1AP60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2026-1AP60/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to the 3RT2026-1AP60?","answer":"The 3RT2027-1AP60 is a direct mechanical and footprint match in the same S0 frame size, with a higher current rating. It swaps in without panel or wiring changes, but verify the current headroom against the load."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2026-1AP60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2026-1AP60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}