{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2027-1AH00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2027-1AH00","canonicalUrl":"https://aoctrl.com/siemens/3RT2027-1AH00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2027-1AH00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S0, 3RT2027-1AH00, rated 27 A at 480 V AC-3, screw-type terminals, 45 mm width, for 35 mm DIN rail.","salesMarkdown":"It carries a 27 A AC-3 rating at 480 V, which means it handles the inrush and running current of a three-phase induction motor up to that load — the rating that governs real-world motor switching, not the higher resistive (AC-1) figure. That buys you options when the gland plate or busbar layout forces an odd angle. Main contacts accept 1–10 mm² solid or stranded (two conductors per terminal: 2x 0.5–1.5 mm² or 2x 0.75–2.5 mm²). Rated for 750 switching cycles per hour in AC-3 duty (motor start/stop), and 1000 cycles/h in AC-1 (resistive). That is typical for a general-purpose S0 contactor — adequate for conveyor, pump, and fan cycling, but not for high-speed indexing or servo-style reversals (those need AC-4 rated gear at 250 cycles/h).","metaTitle":"Siemens SIRIUS 3RT2027-1AH00 Power Contactor, S0, 27 A AC-3","metaDescription":"Siemens SIRIUS 3RT2027-1AH00 power contactor, size S0, rated 27 A AC-3 at 480 V. Screw terminals, 35 mm DIN rail mount. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"97 mm","Solid":"1 ... 10 mm²","Width":"45 mm","at AC":"4 ... 16 ms","Height":"85 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Screw-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"Yes","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"16 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"10 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"5 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"27 A","at 50 Hz rated value":"48 V","at 500 V rated value":"2 A","at 600 V rated value":"27 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"10 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at 575/600 V rated value":"25 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"6.3 W","at AC-2 at 400 V rated value":"15 kW","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"22 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"44 A","at AC-5b up to 400 V rated value":"26.5 A","For Auxiliary And Control Circuit":"screw-type terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 50A (690V,100kA), aM: 25A (690V, 100kA), BS88: 50A (415V, 80kA)","Without Load Current Share Typical":"9.8 W","At Contactor For Auxiliary Contacts":"Screw-type terminals","With Type Of Coordination 1 Required":"gG: 125A (690V,100kA), aM: 50A (690V,100kA), BS88: 125A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"2.3 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"499 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"341 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"260 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"199 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"162 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / P600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"1","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=212362&mlfb=3RT2027-1AH00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2027-1AH00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RT2027-1AH00 and get current pricing?","answer":"It is sourced to order against an RFQ through independent distribution channels. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the AC-3 motor rating at 480 V for this contactor?","answer":"The 3RT2027-1AH00 is rated 27 A at 480 V AC-3, which is the rating that governs motor switching duty. That corresponds to roughly 15–20 kW at 480 V three-phase, depending on motor efficiency and power factor."},{"question":"What compliance documentation does this brand provide?","answer":"The Siemens SIRIUS series carries CE marking for the European market. UL, CSA, and other regional approvals are standard for the SIRIUS line, but specific certification data for this order code should be verified from the manufacturer's declaration or nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2027-1AH00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2027-1AH00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}