{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT2027-2AB04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT2027-2AB04","canonicalUrl":"https://aoctrl.com/siemens/3RT2027-2AB04","factsUrl":"https://aoctrl.com/api/mcp/products/3RT2027-2AB04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT2027-2AB04 power contactor, Size S0, 27 A at 480 V AC-3, spring-type terminals, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"The Siemens 3RT2027-2AB04 is a SIRIUS power contactor in Size S0, rated for 27 A at 480 V AC-3 — that's the motor-switching duty class, so it handles full-load current of a motor up to that rating without welding the contacts on break. The 45 mm width and 102 x 144 mm (H x D) footprint fit standard 35 mm DIN rail per DIN EN 60715, with screw and snap-on fastening. Spring-type terminals on the magnet coil and main contacts accept solid or stranded wire from 1 to 10 mm², and up to 2x (0.5... 2.5 mm²) for the coil terminals — no screwdriver needed for the coil connection, which speeds up panel wiring. The headline 27 A at 480 V is the AC-3 rating — the most common motor-duty curve. That means this contactor can make and break a squirrel-cage motor at full load, up to 27 A, without excessive contact wear.","metaTitle":"Siemens 3RT2027-2AB04 SIRIUS Power Contactor, 27 A at 480 V,","metaDescription":"Siemens SIRIUS 3RT2027-2AB04 power contactor, 27 A rated at 480 V AC-3, Size S0, spring-type terminals, screw and snap-on 35 mm DIN rail. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"144 mm","Solid":"1 ... 10 mm²","Width":"45 mm","at AC":"4 ... 16 ms","Height":"102 mm","Upwards":"10 mm","Forwards":"10 mm","Stranded":"1 ... 10 mm²","at 50 Hz":"0.25","Downwards":"10 mm","Arcing Time":"10 ... 10 ms","At The Side":"6 mm","During Storage":"-55 ... +80 °C","Of Magnet Coil":"Spring-type terminals","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"750 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","Auxiliary Switch":"No","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"750 1/h","For Main Contacts":"18 ... 8","Mounting Position":"+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface","Size Of Contactor":"S0","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Power contactor","at 24 V rated value":"6 A","at 48 V rated value":"2 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 125 V rated value":"0.9 A","at 220 V rated value":"0.3 A","at 230 V rated value":"5 hp","at 400 V rated value":"3 A","at 440 V rated value":"0.6 A","at 480 V rated value":"27 A","at 50 Hz rated value":"24 V","at 500 V rated value":"2 A","at 600 V rated value":"27 A","at 690 V rated value":"1 A","Side-By-Side Mounting":"Yes","For Auxiliary Contacts":"20 ... 14","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"10 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at 575/600 V rated value":"25 hp","Relative Humidity Minimum":"10 %","Of Main Circuit Rated Value":"6 kV","at AC-3 rated value maximum":"690 V","at AC in hot operating state":"6.3 W","at AC-3e rated value maximum":"690 V","at AC-4 at 400 V rated value":"22 A","safety-related switching OFF":"Yes","Substance Prohibitance (Date)":"10/01/2009","Of Auxiliary Circuit Rated Value":"6 kV","at AC-5a up to 690 V rated value":"44 A","at AC-5b up to 400 V rated value":"26.5 A","For Auxiliary And Control Circuit":"spring-loaded terminals","Function Module For Communication":"No","With Type Of Assignment 2 Required":"gG: 50A (690V,100kA), aM: 25A (690V, 100kA), BS88: 50A (415V, 80kA)","Without Load Current Share Typical":"9.8 W","At Contactor For Auxiliary Contacts":"Spring-type terminals","With Type Of Coordination 1 Required":"gG: 125A (690V,100kA), aM: 50A (690V,100kA), BS88: 125A (415V,80kA)","operational current at AC-12 maximum":"10 A","at AC in hot operating state per pole":"2.3 W","for AWG cables for auxiliary contacts":"2x (20 ... 14)","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","mirror contact according to IEC 60947-4-1":"Yes","with low demand rate according to SN 31920":"40 %","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"73 %","Type Of Voltage Of The Control Supply Voltage":"AC","Limited To 1 S Switching At Zero Current Maximum":"499 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 5 S Switching At Zero Current Maximum":"341 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 10 S Switching At Zero Current Maximum":"260 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 30 S Switching At Zero Current Maximum":"199 A; Use minimum cross-section acc. to AC-1 rated value","Limited To 60 S Switching At Zero Current Maximum":"162 A; Use minimum cross-section acc. to AC-1 rated value","contact rating of auxiliary contacts according to UL":"A600 / Q600","Of Main Circuit With Degree Of Pollution 3 Rated Value":"690 V","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value":"690 V","For Short-Circuit Protection Of The Auxiliary Switch Required":"gG: 10 A (500 V, 1 kA)","minimum cross-section in main circuit at maximum AC-1 rated value":"10 mm²","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d48d8b3a648059d9292fcc7e5b5c42d8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=133405&mlfb=3RT2027-2AB04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT2027-2AB04/alternatives.json"},"ai":{"faq":[{"question":"Will 3RT2027-2AB04 drop into a panel specified around 3RT2027-2AG24 without rewiring?","answer":"The 3RT2027-2AB04 shares the same Size S0 footprint (45 mm width, same DIN-rail mounting) and spring-type terminals as the 3RT2027-2AG24. The key difference is the coil voltage: the -2AB04 is a 24 VDC coil variant, while the -2AG24 is a 230 VAC coil variant. If the panel's control voltage matches 24 VDC, it drops in without rewiring; if the original spec called for 230 VAC coil supply, you'll need to swap the coil supply or choose the correct coil variant."},{"question":"What is 3RT2027-2AB04's depth?","answer":"The depth is 144 mm."},{"question":"What wire sizes does the 3RT2027-2AB04 accept?","answer":"Main terminals accept solid or stranded wire from 1 to 10 mm². Coil terminals accept 2x (0.5... 2.5 mm²) solid or stranded. All terminals are spring-type — no screwdriver needed for the coil connection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT2027-2AB04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT2027-2AB04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}